[Setup of failed outdoor unit]
(13)When the low-pressure sensor output of the failed outdoor unit falls below 0.10MPa, fully close the balance
pipe packed valve, and press SW05 on the interface P.C. board to finish the pump-down operation.
(14)Turn off the power supply to all the outdoor units, and recover the residual refrigerant in the outdoor unit using
a refrigerant recovery device. Be sure to measure the amount of recovered refrigerant. (This is necessary to
determine how much additional refrigerant will be needed after the completion of the repair.)
This is the end of the refrigerant recovery operation.
Set SW01/02/03 of the failed outdoor unit and the outdoor unit for pressure adjustment back to 1/1/1.
Failed outdoor unit
Unit for pressure adjustment
(9)
(6)
(11)
(12)
(14)
(13)
Approx. 10 minutes after system startup,
fully close gas pipe service valve.
(8)
Select outdoor unit with lowest unit No.
as outdoor unit for pressure adjustment.
Fully close balance pipes of all outdoor
units other than unit for pressure
adjustment and failed unit.
While monitoring low-pressure
sensor output, adjust pressure to
around 0.12 MPa by slowly closing
gas pipe service valve.
When low-pressure sensor output of failed
outdoor unit falls below 0.10 MPa, fully close
balance pipe packed valve.
Press SW05 to finish pump-down operation.
Turn off power supply to all outdoor units at
source, and recover residual refrigerant in
outdoor unit using refrigerant recovery device.
Measure amount of recovered refrigerant.
Wait until low-pressure sensor
outputs of failed outdoor unit and
outdoor unit for pressure
adjustment become almost
identical, and, after letting system
continue operating for while longer,
fully close gas pipe service valve.
(7)
Press SW04 to have
low-pressure sensor
output displayed
[Ps] [###]
(10)
Set SW01/02/03 to
1/2/2 to have low-
pressure sensor
output displayed.
[Ps] [###]
Summary of Contents for MMY-MAP0804HT7JP
Page 23: ... 22 1 Wiring Diagrams 1 1 Outdoor Unit Models MMY MAP0804 MAP1004 and MAP1204 ...
Page 24: ... 23 Models MMY MAP1404 and MAP1604 ...
Page 35: ... 34 1 2 10 Slim Duct Type AP024 AP027 Models MMD AP0244SPH MMD AP0274SPH ...
Page 38: ... 37 1 2 13 High Wall Type 3 series Models MMK AP0073H AP0093H AP0123H AP0153H AP0183H AP0243H ...
Page 52: ... 51 2 5 Parts Layout in Outdoor Unit 8 10 12HP Model MMY MAP0804 MAP1004 MAP1204 ...
Page 53: ... 52 14 16HP Model MMY MAP1404 MAP1604 ...
Page 57: ... 56 2 7 2 Inverter P C board for compressor MCC 1596 A3 IPDU ...
Page 323: ......