– 158 –
7-7-8. Fan Operation Check in Outdoor Unit
This function is provided to check the fan operation of the outdoor unit by using switches on the interface P.C. board
in the outdoor unit. The frequency of the fan speed can be controlled by setting of the switches. Use this function
to check the operation or abnormal sound in the fan system. And, use this function while the system is stopped.
NOTE)
Do not use this function during operation of the compressor. It may damage the compressor.
[Operation]
(1) Set the switches SW01/SW02/SW03 on the interface P.C. board of the outdoor unit to [2/1/4].
(2) When [F. d] is displayed in 7-segment display [A], keep pressing the switch SW04 for 2 seconds or more.
(3) When [ 63 ] is displayed in 7-segment display [B], the fan starts operation. (Max. mode operation)
(4) After that, by changing the setup number of the switches SW02 and SW03, 7-segment display [B] and the fan
mode are changed.
(Mode output pattern of the fan is as follows.)
[Clear]
This function is cleared by one of the following operations.
(1) When SW01 setting number was changed to other number.
(2) Press-switch SW05 was pressed for 2 seconds or more.
SW02 SW03
7-segment display [B]
Fan mode
1
4
[ 63 ]
63
2
[ 62 ]
62
3
[ 61 ]
61
4
[ 60 ]
60
5
[ 59 ]
59
6
[ 58 ]
58
7
[ 57 ]
57
8
[ 56 ]
56
9
[ 55 ]
55
10
[ 54 ]
54
11
[ 53 ]
53
12
[ 52 ]
52
13
[ 51 ]
51
14
[ 50 ]
50
15
[ 49 ]
49
16
[ 48 ]
48
1
5
[ 47 ]
47
2
[ 46 ]
46
3
[ 45 ]
45
4
[ 44 ]
44
5
[ 43 ]
43
6
[ 42 ]
42
7
[ 41 ]
41
8
[ 40 ]
40
9
[ 39 ]
39
10
[ 38 ]
38
11
[ 37 ]
37
12
[ 36 ]
36
13
[ 35 ]
35
14
[ 34 ]
34
15
[ 33 ]
33
16
[ 32 ]
32
SW02 SW03
7-segment display [B]
Fan mode
1
6
[ 31 ]
31
2
[ 30 ]
30
3
[ 29 ]
29
4
[ 28 ]
28
5
[ 27 ]
27
6
[ 26 ]
26
7
[ 25 ]
25
8
[ 24 ]
24
9
[ 23 ]
23
10
[ 22 ]
22
11
[ 21 ]
21
12
[ 20 ]
20
13
[ 19 ]
19
14
[ 18 ]
18
15
[ 17 ]
17
16
[ 16 ]
16
1
7
[ 15 ]
15
2
[ 14 ]
14
3
[ 13 ]
13
4
[ 12 ]
12
5
[ 11 ]
11
6
[ 10 ]
10
7
[ 9 ]
9
8
[ 8 ]
8
9
[ 7 ]
7
10
[ 6 ]
6
11
[ 5 ]
5
12
[ 4 ]
4
13
[ 3 ]
3
14
[ 2 ]
2
15
[ 1 ]
1
16
[ 0 ]
0
Summary of Contents for MMY-MAP0804HT7JP
Page 23: ... 22 1 Wiring Diagrams 1 1 Outdoor Unit Models MMY MAP0804 MAP1004 and MAP1204 ...
Page 24: ... 23 Models MMY MAP1404 and MAP1604 ...
Page 35: ... 34 1 2 10 Slim Duct Type AP024 AP027 Models MMD AP0244SPH MMD AP0274SPH ...
Page 38: ... 37 1 2 13 High Wall Type 3 series Models MMK AP0073H AP0093H AP0123H AP0153H AP0183H AP0243H ...
Page 52: ... 51 2 5 Parts Layout in Outdoor Unit 8 10 12HP Model MMY MAP0804 MAP1004 MAP1204 ...
Page 53: ... 52 14 16HP Model MMY MAP1404 MAP1604 ...
Page 57: ... 56 2 7 2 Inverter P C board for compressor MCC 1596 A3 IPDU ...
Page 323: ......