– 18 –
Adding refrigerant
After finishing vacuuming, exchange the vacuum pump with a refrigerant canister and start additional charging of
refrigerant.
Calculation of additional refrigerant charge amount
Refrigerant charge amount at shipment from the factory does not include the refrigerant for pipes at the local site.
For refrigerant to be charged in pipes at the local site, calculate the amount and charge it additionally.
NOTE
If the additional refrigerant amount indicates minus as the result of calculation, use the air conditioner without
additional refrigerant.
Table 1
Heat pump
type
Outdoor unit type
MAP080
MAP100
MAP120
MAP140
MAP160
Charging amount (kg)
11.5
Cooling only
type
Outdoor unit type
MAP080
MAP100
MAP120
MAP140
MAP160
Charging amount (kg)
10.5
10.5
10.5
11.5
11.5
Additional refrigerant charge
amount at local site
=
Real length of liquid pipe
×
Additional refrigerant charge
amount per 1m liquid pipe
(Table 1)
+
Corrective amount of refrigerant
depending on HP of co-
operating outdoor units
(Table 2)
2
.
2
2
1
.
9
1
9
.
5
1
7
.
2
1
5
.
9
4
.
6
)
m
m
(
.
a
i
d
e
p
i
p
d
i
u
q
i
L
Additional refrigerant amount/1m liquid
pipe (kg/m)
0.025
0.055
0.105
0.160
0.250
0.350
Summary of Contents for MMY-MAP0804HT7JP
Page 23: ... 22 1 Wiring Diagrams 1 1 Outdoor Unit Models MMY MAP0804 MAP1004 and MAP1204 ...
Page 24: ... 23 Models MMY MAP1404 and MAP1604 ...
Page 35: ... 34 1 2 10 Slim Duct Type AP024 AP027 Models MMD AP0244SPH MMD AP0274SPH ...
Page 38: ... 37 1 2 13 High Wall Type 3 series Models MMK AP0073H AP0093H AP0123H AP0153H AP0183H AP0243H ...
Page 52: ... 51 2 5 Parts Layout in Outdoor Unit 8 10 12HP Model MMY MAP0804 MAP1004 MAP1204 ...
Page 53: ... 52 14 16HP Model MMY MAP1404 MAP1604 ...
Page 57: ... 56 2 7 2 Inverter P C board for compressor MCC 1596 A3 IPDU ...
Page 323: ......