– 150 –
(2) Heating test operation function
This function is provided to change collectively the mode of all the indoor units connected to the same system for
the heating test operation mode, by using switches on the interface board of the header unit.
<Operation procedure>
0
NOTE)
The test operation returns to the normal operation after 60 minutes.
[
A
]
[H.
]
[
B
]
[
–
H]
Power ON
Start
Operation check
Stop/End
Press SW04 on the same board for 2 seconds or more.
[Test run] is displayed on the remote controller of
the indoor unit to be operated. Check that [ – H]
is displayed on 7-segment display [B] on the
interface P.C. board of the header unit.
Set SW01/SW02/SW03 on the interface P.C. board of the header unit
to [2/6/1].
([H ] is displayed on 7-segment display [A].)
Be sure to turn on power at the indoor side
before power-ON of outdoor unit.
Return SW01/SW02/SW03 on the interface P.C. board of the header
unit to [1/1/1],
or press the push-switch SW05 for 2 seconds or more.
7-segment display [A]
7-segment display [B]
SW04
SW05
<Rotary switches>
SW02
SW03
SW01
Summary of Contents for MMY-MAP0804HT7JP
Page 23: ... 22 1 Wiring Diagrams 1 1 Outdoor Unit Models MMY MAP0804 MAP1004 and MAP1204 ...
Page 24: ... 23 Models MMY MAP1404 and MAP1604 ...
Page 35: ... 34 1 2 10 Slim Duct Type AP024 AP027 Models MMD AP0244SPH MMD AP0274SPH ...
Page 38: ... 37 1 2 13 High Wall Type 3 series Models MMK AP0073H AP0093H AP0123H AP0153H AP0183H AP0243H ...
Page 52: ... 51 2 5 Parts Layout in Outdoor Unit 8 10 12HP Model MMY MAP0804 MAP1004 MAP1204 ...
Page 53: ... 52 14 16HP Model MMY MAP1404 MAP1604 ...
Page 57: ... 56 2 7 2 Inverter P C board for compressor MCC 1596 A3 IPDU ...
Page 323: ......