– 139 –
7-5-4. In checking the number of connected outdoor units and
connected indoor units after address setup, a lower number of
connected units is displayed. (There are outdoor/indoor units
that do not operate in a test operation.)
s
e
r
u
s
a
e
m
r
e
t
n
u
o
C
e
s
u
a
C
s
u
t
a
t
S
The number of
connected
outdoor units is
too few.
Miswiring of communication lines between outdoor units
or an unconnected wire ( Fig. 4). (Address setup
operation finished without recognizing a miswired
follower unit.)
After modification of wiring, set up the addresses again and
check the number of connected outdoor units.
The number of
connected indoor
units is too few.
Miswiring of communication lines between indoor units
or an unconnected wire ( Fig. 5). (Address setup
operation finished without recognizing a miswired indoor
unit.)
After modification of wiring, set up the addresses again and
check the number of connected indoor units.
The number of
outdoor units
connected to a
group is too few in
group operation
from an indoor
remote controller.
The indoor remote controller is not connected with wire.
Miswiring of the indoor remote controller
Using the main indoor remote controller connected to a group,
start a test operation, specify the unit that is not operating (the
unit not connected to the group), and then check the wiring.
Indoor remote controller communication circuit error
If 220-240 V is incorrectly applied to the remote controller
terminal, the remote controller communication circuit
fails.
Using the main indoor remote controller connected to a group,
start a test operation and then specify the unit that is not
operating (the unit not connected to the group). Remove the
fast-on terminal connected to remote controller terminals A/B,
and check the voltage. If voltage is not applied (normally 15
to18 V), replace the PC board.
Summary of Contents for MMY-MAP0804HT7JP
Page 23: ... 22 1 Wiring Diagrams 1 1 Outdoor Unit Models MMY MAP0804 MAP1004 and MAP1204 ...
Page 24: ... 23 Models MMY MAP1404 and MAP1604 ...
Page 35: ... 34 1 2 10 Slim Duct Type AP024 AP027 Models MMD AP0244SPH MMD AP0274SPH ...
Page 38: ... 37 1 2 13 High Wall Type 3 series Models MMK AP0073H AP0093H AP0123H AP0153H AP0183H AP0243H ...
Page 52: ... 51 2 5 Parts Layout in Outdoor Unit 8 10 12HP Model MMY MAP0804 MAP1004 MAP1204 ...
Page 53: ... 52 14 16HP Model MMY MAP1404 MAP1604 ...
Page 57: ... 56 2 7 2 Inverter P C board for compressor MCC 1596 A3 IPDU ...
Page 323: ......