– 42 –
Check code
Typical fault site
Description of error
P07
P07
—
Heat sink overheating error
Temperature sensor built into IGBT (TH) detects overheating.
A01
Flow switch protective operation
A01
—
• Check the pump.
• Check the strainer.
• Check the flow switch.
(Type, directtion of attachment and point of contact)
P20
P20
—
High-pressure protection
activation
High-pressure (Pd) sensor detected a value over the criteria.
P15
P15
01: TS condition
02: TD condition
Gas leak detection
Outdoor suction temperature sensor (TS1) detects sustained and
repeated high temperatures that exceed standard value.
P17
P17
—
Outdoor discharge (TD2)
temperature error
Outdoor discharge temperature sensor (TD2) detects abnormally
high temperature.
P18
P18
—
Outdoor discharge (TD3)
temperature error
Outdoor discharge temperature sensor (TD3) detects abnormally
high temperature.
P19
P19 Outdoor unit No. detected
4-way valve reversing error
Abnormality in refrigerating cycle is detected during heating
operation.
P20
P20
—
Activation of high-pressure
protection
High pressure (Pd) sensor detects high pressure that exceeds
standard value.
P22
P22
SMMS-i (Series 4)
0..: IGBT circuit
1..: Position detection circuit error
3..: Motor lockup error
4..: Motor current detection
C..: TH sensor error
D..: TH sensor error
E..: Inverter DC voltage error
(outdoor fan)
Note: Although letters 0 to F
appear at locations indicated
by "
∗
", please ignore them.
Outdoor fan IPDU error
Outdoor fan IPDU detects error.
P26
P26
01: Compressor 1
02: Compressor 2
03: Compressor 3
Activation of G-Tr (IGBT) short-
circuit protection
Short-circuit protection for compressor motor driver circuit
components is activated (momentary overcurrent).
F13
F13
01: Compressor 1
02: Compressor 2
03: Compressor 3
Error in temperature sensor built
into indoor IGBT (TH)
Temperature sensor built into indoor IGBT (TH) has been open /
short-circuited.
(P10)
P10 Indoor unit No. detected
Indoor unit overflow
Indoor unit has been shutdown in one refrigerant line due to
detection of overflow (detected by indoor unit).
P13
P13
—
Outdoor liquid backflow detection
error
State of refrigerant cycle circuit indicates liquid backflow operation.
P29
P29
01: Compressor 1
02: Compressor 2
03: Compressor 3
Compressor position detection
circuit error
Compressor motor position detection error is detected.
H01
H01
01: Compressor 1
02: Compressor 2
03: Compressor 3
Compressor breakdown
Inverter current (Idc) detection circuit detects overcurrent.
H02
H02
01: Compressor 1
02: Compressor 2
03: Compressor 3
Compressor error (lockup)
Compressor lockup is detected
H03
H03
01: Compressor 1
02: Compressor 2
03: Compressor 3
Current detection circuit error
Abnormal current is detected while inverter compressor is turned
off.
P04
P04
01: Compressor 1
02: Compressor 2
03: Compressor 3
Activation of high-pressure SW
High-pressure SW is activated.
P07
P07
01: Compressor 1
02: Compressor 2
03: Compressor 3
Heat sink overheating error
Temperature sensor built into IGBT (TH) detects overheating.
P05
P05
00: Open phase detected
Open phase / power failure
01: Compressor 1 ALT
02: Compressor 2
03: Compressor 3
Inverter DC voltage (Vdc) error
MG-CTT error
Open phase is detected when power is turned on.
Inverter DC voltage is too high (overvoltage) or too
low (undervoltage).
TCC-LINK
central control
or main remote
controller
display
Outdoor 7-segment display
Sub-code
MG-CTT: Magnet contactor
Indoor unit (including Hot Water Module)
(L30)
L30 Detected indoor unit No.
Indoor external error input
(interlock)
Indoor unit has been shut down for external error input in one
refrigerant line (detected by indoor unit).
P03
—
Outdoor discharge (TD1)
temperature error
Outdoor discharge temperature sensor (TD1) has detected
abnormally high temperature.
P04
P04
P0301: Compressor 1
02: Compressor 2
03: Compressor 3
High-pressure SW
activation
High-pressure SW was activated.