– 30 –
4
Push the TIME
/
buttons repeatedly to change the value of the indoor unit address in
SET DATA.
Change the value in SET DATA to that of a new address.
5
Push the button to confirm the new address on SET DATA.
6
Push the
UNIT LOUVER
button (left side of the button) repeatedly to select another address to
change.
Each time you push the button, the indoor unit numbers in a refrigerant line are indicated
one after another. Only the fan and louvers of the selected indoor unit are activated.
Repeat steps
4
to
6
to change the indoor unit addresses so as to make each of them unique.
7
Push the button.
(All the segments on the LCD display light up.)
8
Push the button to finish the procedure.
NOTE:
The LED on the P.C. board of the selected hot water module flashes. The hot water module for change
settings can be confirmed.
SET
TIME
TIMER SET
TEST
FILTER
RESET
CL
FAN
SAVE
SWING/FIX
VENT
MODE
ON / OFF
UNIT LOUVER
4
6
8
5, 7
Press to finish setting
TEMP.
CODE NO.
Finish