– 33 –
Target outdoor unit (SMMS-i – Series 4) for hot water module
CODE No.
Data
Format
Unit
Remote controller display example
Hot water
module *2
00
Water inlet temperature (in control)
×1
˚C
[0024]=24 ˚C
02
Water inlet Temperature (TA)
×1
˚C
03
Heat exchanger Temperature (TCJ)
×1
˚C
04
Water outlet Temperature (TC2)
×1
˚C
05
Heat exchanger Temperature (TC1)
×1
˚C
06
Heat exchanger temperature (TF) *1
×1
˚C
08
PMV
×1/10
pls
[0150]=1500 pls
F9
Air Suction Temperature of direct expansion
coil (TSA) *1
×1
˚C
[0024]=24 ˚C
FA
Outdoor Air Temperature (TOA) *1
×1
˚C
System
data
0A
Number of connected indoor units
×1
–
[0048]=48
0B
Total horse power of connected indoor units
×10
HP
[0415]=41.5HP
0C
Number of connected outdoor units
×1
–
[0004]=4
0D
Total horse power of outdoor units
×10
HP
[0420]=42HP
CODE No.
Data
Format
Unit
Remote controller display example
U1 U2 U3 U4
Individual
data 1 of
outdoor unit
*3
10 20 30
40
Detection pressure of high-pressure sensor
(Pd)
×100
MPa
[0123]=1.23 MPa
11 21 31
41
Detection pressure of low-pressure sensor
(Ps)
×100
MPa
12 22 32
42
Discharge temperature of compressor 1
(Td1)
×1
˚C
[0024]=24 ˚C
13 23 33
43
Discharge temperature of compressor 2
(Td2)
×1
˚C
14 24 34
–
Discharge temperature of compressor 3
(Td3)
×1
˚C
15 25 35
45 Suction Temperature (TS)
×1
˚C
16 26 36
46 Coil Temperature 1 (TE1)
×1
˚C
17 27 37
–
Coil Temperature 2 (TE2)
×1
˚C
18 28 38
48 Liquid Temperature (TL)
×1
˚C
19 29 39
49 Outdoor Temperature (TO)
×1
˚C
1A 2A 3A 4A PMV1 + 2
×1
pls
[0050]=500 pls
1B 2B 3B
–
PMV4
×1
pls
1C 2C 3C 4C Current of compressor 1 (I1)
×10
A
[0135]=13.5 A
1D 2D 3D 4D Current of compressor 2 (I2)
×10
A
1E 2E 3E
–
Current of compressor 3 (I3)
×10
A
1F 2F 3F 4F Outdoor fan current (IFan)
×10
A
*1 The TF/TSA/TOA sensors are equipped only with some types of indoor units. The data does not appear for
other types.
*2 In the case of group connection, only the header indoor unit data can be displayed.
*3 The upper digit of CODE No. indicates the outdoor unit No.
*4 [(The upper digit of CODE No.) – 4] indicates the outdoor unit No.
1
∗
, 5
∗
... U1 outdoor unit (Header unit)
2
∗
, 6
∗
... U2 outdoor unit (follower unit 1)
3
∗
, 7
∗
... U3 outdoor unit (follower unit 2)
4
∗
, 8
∗
... U4 outdoor unit (follower unit 3)
*5 Only CODE No. 5
∗
of U1 outdoor unit (Header unit) is displayed.