Basic Installation and Operation Guide
JK 400 Series Fixed Controllers
TOSHIBA
25
CONTROLLER RATINGS
Table 2 Short-Circuit & Withstand Capability
Interrupting
Capacity
(Sym.
Amperes)
Interrupting
Capacity
(Sym. MVA)
Short Time
Capability
30 Seconds
Short Time
Capability
1 Second
Dielectric
Withstand
1 Minute
Impulse
Voltage
Withstand
50,000 RMS
@2.3-6.6kV
(7.2kV Max)
[email protected]
[email protected]
[email protected]
2400 A
6,000 A
AC 19 kV
DC 26kV
60 kV BIL
Table 3 Continuous Current Rating
Enclosure Type
Max. Continuous
Amperes
One
-
High Controller
Max. Continuous Amperes
Lower Controller in a Two-
High Stacking Arrangement
Max. Continuous Amperes
Upper Controller in a Two-
High
Stacking Arrangement
Type-1
Ventilated
360
360
320
Type-1 Non-
Ventilated
320
320
280
Type-12, 3R
310
310
280