32
G8000MM
Installation and Operation Manual
Terminals 9 to 18
"Spare" contact input (IN5 through IN9)
Terminals 19 to 20
"Remote EPO" contact input
Used to perform a remote UPS Emergency Power Off (EPO).
The load will be dropped.
The UPS is equipped with a selectable output contact item.
The above items are the default settings.
Contact Toshiba International Corporation
for setup information
.
In all cases, a switch having a protective cover is recommended in
order to reduce the possibility of accidental operation
.
2.5 External communication connector
This is an RS232C port for “RemotEyeII”* monitoring software.
The layout of connector is shown in Figure 2.18.
FIGURE 2.18
External communication connector (NEC Class2)
Pin 1.
: Not used
Pin 2. RXD
: Receive data
Pin 3. TXD
: Transmit data
Pin 4.
: Not used
Pin 5. GND
: Signal ground
Pin 6.
: Not used
Pin 7.
: Not used
Pin 8.
: Not used
Pin 9.
: Not used
* Consult Toshiba International Corporation for details on
“
RemotEyeII
”
monitoring software and
its capabilities.
D-SUB 9Pin (male)
PCB IOAU-04
1
2
3
4
5
6
7
8
9
CAUTION
!
NOTE