78
G8000MM
Installation and Operation Manual
Installation Planning Guide for G8000MM 300kVA UPS
Standard System: 480V Input, 480Y/277V Output
General Mechanical Information
Dimensions
(W x D x H*)
Weight
Floor
Loading
Approximate Full-Load
Heat Rejection
Mechanical Clearance (Inches)from UPS
for Ventilation and Maintenance Access
Inches
Lbs.
Lbs./ft.
2
Btu/Hr
Top
Front
Bottom Sides**
Back
76.8” x 37.7” x 79.7” 4,564
229
60,894
24”
43”
0”
1”
0”
* Height includes removable fan housing – Frame height is 78.7.”
** 0” clearance for peripheral equipment, 1” clearance for walls.
Primary AC Input (480V 3-Phase / 3-Wire)
Maximum Input Power Demand
Normal Mode (Recharge Mode)
Suggested External
Overcurrent Protection
External Feeder Wire Size: Min. – Max. Per Phase
kVA
PF
Amps
Amps
AWG or kcmil at 75º C Temp. Rating
294 (312)
>0.98
353 (376)
500 AT
(2) x 250 kcmil – (2) x 300 kcmil
Alternate (Bypass) AC Input (480V 3-Phase / 4-Wire)
Maximum Input Power
Demand
Suggested External
Overcurrent Protection
External Feeder Wire Size:
Min. – Max. Per Phase // Min. – Max. for Neutral
kVA
PF
Amps
Amps
AWG or kcmil at 75º C Temp. Rating
300
0.9
361
500 AT
(2) x 250 kcmil – (2) x 300 kcmil //
(2) 500 kcmil – (3) x 300 kcmil
Battery Input (480VDC Nominal)
Battery Capacity Required
for Full Load Output
Maximum Discharge
at Full Load Output
Suggested External
Overcurrent Protection
External Feeder Wire Size: Min. – Max.
kWB
Amps DC
Amps
AWG or kcmil at 75º C Temp. Rating
289
720
800 AT
(3) 250 kcmil – (3) x 350 kcmil
AC Output (480/277V 3-Phase / 4-Wire)
Rated Output Power
Suggested External
Overcurrent Protection
External Feeder Wire Size:
Min. – Max. Per Phase // Min. – Max. for Neutral
kVA
PF
Amps
Amps
AWG or kcmil at 75º C Temp. Rating
300
0.9
361
500 AT
(2) x 250 kcmil – (2) x 300 kcmil //
(2) 500 kcmil – (3) x 300 kcmil
Important Notes:
1.
Maximum Current required at Primary AC Input based on
full load output and maximum battery charging current.
2.
Output load conductors are to be installed in separate
conduit from input conductors.
3.
Control wires and power wires are to be installed in
separate conduits.
4.
Recommended AC input and output overcurrent protection
based on continuous full load current per NEC.
5.
Wiring shall comply with all applicable national and local
electrical codes.
6.
Grounding conductors to be sized per NEC Article
250-122. Neutral conductors to be sized per NEC Article
310.15.
-
Primary AC Input: 3 , 3-wire + ground.
-
Alternate AC Input: 3 , 4-wire + ground.
-
AC Output: 3 , 4-wire + ground.
-
DC Input: 2-wire (Positive/Negative) + ground.
7.
Nominal battery voltage based on the use of VRLA type
batteries (2.0 volts/cell nominal).
8.
Maximum battery discharge current based on lowest
permissible discharge voltage of 1.67 VPC.
9.
DC wires should be sized to allow not more than a 2-volt
drop at maximum discharge current.
10. Weights do not include batteries or other auxiliary equipment
external to the UPS.
11. Cable sizing calculations based on the following assumptions:
-
Minimum size is smallest size based on ampacity at 30 C.
-
No more than three current carrying conductors per conduit.
-
Neutral sized for 2 X phase current.
-
Temperature rating of copper conductors/terminals: 75 C.
-
Reference: 2005 NEC Handbook, Table 310.16.
NOTE: Consult latest edition of applicable
national and local codes for possible
variations.
12. Ratings of wires and overcurrent devices are suggested
minimums. Consult with a registered Professional Engineer
within your local area for proper size selections.
TOSHIBA
INTERNATIONAL CORPORATION
13131 West Little York Road
Houston, TX 77041
Telephone: (800) 231-1412
Fax: (713) 896-5212
Web Site:
1/3