20
G8000MM
Installation and Operation Manual
TABLE 1.6
Rating of Contactors and Fuses
NUMBER
APPLICATION
OUTPUT CAPACITY OF EQUIPMENT
100kVA
150kVA
225kVA
300kVA
375kVA
500kVA
625kVA
750kVA
480V 600V 480V 600V 480V 600V 480V 600V 480V 600V 480V 600V 480V 600V 480V 600V
Con
ta
cto
r,
Bre
a
ke
r
CB1
AC input contactor
135A
200A
350A
450A
660A
660A
910A
CB2
Battery disconnect breaker
225
350A
500A
800A
900A
1200A
1600A
2000
CB3
STS contactor
135A
260A
52C
Inverter output
contactor
135A
200A
350A
450A
450A
660A
910A
52S
Bypass contactor
135A
200A
350A
450A
450A
660A
910A
88RC
Control circuit contactor
90A
F
u
se
s
FCU, FCV, FCW
AC input fuse
200A-690V
250A-690V
315A-690V
FDU,FDV,FDW
FDX,FDY,FDZ
FDP,FDN
DC arm fuse
450A-690V 450A-690V 630A-690V 900A-550V 900A-550V 630A-690V
900A-550V
FUA, FUB, FUC
Control power fuse
30A-600V
(OPTION)
FSU, FSV, FSW
Bypass input fuse
200A-
690V
-
315A-
690V
-
250A-
690V
-
250A-
690V
-
315A-
690V
-
315A-
690V
-
315A-
690V
-
315A-
690V
-
FZS1, 2, 3
Bypass input ZNR fuse
5A- 500V
FBS1, 2, 3
Control power fuse
10A-600V
FZR1, 2, 3
AC input ZNR fuse
5A- 500V
FPU, FPV, FPW
Parallel control
circuit fuse
3A- 600V
*Rating would be changed.