4-4-4 Setting for Energy monitoring relay interface
ON
SW1
SW2
SW3
LED2
LED3
LED4
LED5
LED1
SW4
SW7
1 2 3 4
DI1
DI2
DI3
DI4
DI5
DI6
DI7
DI8
NL
B
A
RS-485
• SW2 Operation mode set switch
• SW3 Test switch
• SW4 Test switch
• SW7 Reset switch
When performing a address setting with SW1, push this reset switch after the address setting to
read the set value.
CAUTION
• Set relay interface addresses according to the air conditioner address table.
• When the SW1 setting has been changed, push reset switch SW7. The new address
setting is read.
• You can set the Energy Monitoring Relay Interface address independently from the TCS-
NET Relay Interface address or the Digital I/O Relay Interface address.
The following settings are necessary to use Energy Monitoring Relay Interfaces.
• SW1 Address set switch
When two or more Energy Monitoring Relay Interfaces are used, set a different address for each
unit to avoid address duplication.
Assign addresses in an ascending order. (from 1, 2, 3 . . . n)
These switches are not used during normal
operation. Set zero (0) or "all OFF".
SW1
SW2
SW3
SW4
SW7
LED1
LED2
LED3
LED4
LED5
Address set switch
1 - 4
Address
0,5 - F
Not used
Operating mode set switch (0 usually)
Test switch (all OFF usually)
Test switch
Reset switch
Power indicator
RS-485 communication status indicator
Not used
Test indicator
Test indicator
Summary of Contents for BMS-TP0640ACE
Page 1: ...FILE NO A04 016 TCS NET AIR CONDITIONING CONTROL SYSTEM TOUCHSCREENCONTROLLER TENTATIVE ...
Page 16: ...16 ...
Page 17: ...17 2 SYSTEM CONFIGURATION 2 1 Touch screen controller system configuration ...
Page 22: ...22 ...
Page 54: ...54 ...
Page 96: ...96 ...
Page 103: ...103 ...
Page 104: ......