13
PC operating environment
1-5 Energy monitoring and billing function
Distributes total power consumption for each indoor unit according to the billing schedule set by the Touch
Screen Controller. Reads the system setup file and the operation result file saved in the CF card of the
Touch Screen Controller into the PC, and calculates power distribution result using the dedicated report
creation software (Excel macro) to create spreadsheets and monthly reports.
Excel
HUB
IF
Ethernet
Ethernet
RS-485
Main BUS
Setup file creation
software
Setup file
Software under
development
Setup file
• Tenant name, etc.
• Air conditioner information, etc.
• Setting values for energy
monitoring and billing
Air conditioner specific
characteristic values
Tenant names for reports
File transfer (FTP)
Monthly meter-read
file
Setup file
Report creation software
(Excel macro)
Default data file
Air conditioner operation result
Power meter pulse counter value
Record in
CF card
Every
15 min
Touch Screen
Controller
Monthly report, spreadsheet
(Excel file)
Intelligent Server
Energy
monitoring I/F
Power meter
Air conditioner
Energy
monitoring
and billing
software
PC (procured on site)
Printer
Printer for monthly reports
(procured on site)
Windows 2000 or later
Excel 2000 or later is required separately.
OS
Excel
A PC for energy monitoring and billing and a printer should be procured on site.
Touch Screen Controller sets a billing schedule for monthly reports.
Data flow
Specifications
Electricity billing schedule
Summary of Contents for BMS-TP0640ACE
Page 1: ...FILE NO A04 016 TCS NET AIR CONDITIONING CONTROL SYSTEM TOUCHSCREENCONTROLLER TENTATIVE ...
Page 16: ...16 ...
Page 17: ...17 2 SYSTEM CONFIGURATION 2 1 Touch screen controller system configuration ...
Page 22: ...22 ...
Page 54: ...54 ...
Page 96: ...96 ...
Page 103: ...103 ...
Page 104: ......