4-3-1 (14) In case of increase the address-undefined indoor units (Extension, etc.)
If set up the indoor address of which address is undefined accompanied with extension of indoor units,
replacement of P.C. board, etc, follow to the methods below.
Method 1
Set up an address individually from a wired remote controller.
(Line address, Indoor address, Group address, Central control address)
For the setup method, refer to the above “Manual address setup from remote controller”.
Method 2
Set up an address from the outdoor unit.
∗
Leave the address of the unit of which address has been already set up as it is.
Set up an address only to the unit of which address is undefined.
The addresses are allocated from the low number.
Setup procedure
Arrange the outdoor header units in the refrigerant line to which indoor units are added. (Figure below)
1. Remove the relay connector between [U1U2] and [U3U4].
2. Turn on SW30-2 on the interface P.C. board at outdoor header unit side if it is ON.
∗
Turn off the power, and then execute the operation.
“AUTO1”
→
“AUTO2”
→
“AUTO3” … is counted and displayed on 7-degment display.
5. When “U.1. - - -” is displayed on 7-segment display, the setup operation finished.
Turn off the indoor/outdoor power.
6. Return the following setup as before.
• Relay connector
• SW30-2
• SW01, 02, 03
U3 U4
U1 U2
U5 U6
U1 U2
A B
Header unit
Remote
controller
U3 U4
U1 U2
U5 U6
U1 U2
A B
Follower unit
Remote
controller
U3 U4
U1 U2
U5 U6
U1 U2
A B
Remote
controller
U3 U4
U1 U2
U5 U6
U1 U2
A B
Follower unit
U3 U4
U1 U2
U1
U3
U2
U4
U5 U6
U1 U2
A B
Remote
controller
Center unit
Center unit
Center unit
Center unit
Header unit
Header unit
Central control
device
Added indoor unit
Disconnect
3. Turn on the indoor/outdoor power of which address is to be set up. After approx. 1 minute, check that
“U.1.---” is displayed on 7-segment display.
4. Execute the following operation on the interface P.C. board of the header outdoor unit.
SW04
After checking that “In.At” is displayed on 7-segment
display, and then push SW04 for 5 seconds or more.
SW01 SW02 SW03
2
14
2
Summary of Contents for BMS-TP0640ACE
Page 1: ...FILE NO A04 016 TCS NET AIR CONDITIONING CONTROL SYSTEM TOUCHSCREENCONTROLLER TENTATIVE ...
Page 16: ...16 ...
Page 17: ...17 2 SYSTEM CONFIGURATION 2 1 Touch screen controller system configuration ...
Page 22: ...22 ...
Page 54: ...54 ...
Page 96: ...96 ...
Page 103: ...103 ...
Page 104: ......