TOSHIBA
"LOW" CONTACTS
63
assign function to "LOW"
0 - 63
1
4
9-10
FUNCTION
contact
5-1
"LOW" CONTACTS
64
"LOW" output contact
1 - 100
1
1
9-10
DELAY TIME
delay time
5-1
"LOW" CONTACTS
65
"LOW" output contact
1 - 100
1
1
9-10
HOLD TIME
hold time
5-1
"FL" CONTACTS
66
asssign function to "FL" output
0 - 63
1
10
9-10
FUNCTION
contact
5-1
"FL" CONTACTS
67
"FL" output contacts
1 - 100
1
1
9-10
DELAY TIME
delay time
5-1
"FL" CONTACTS
68
"FL" output contacts
1 - 100
1
1
9-10
HOLD TIME
hold time
5-1
"OUT" CONTACTS
69
assign function to "OUT"
0 - 61
1
8
9-10
FUNCTION
output contacts
(available on option board)
"OUT" CONTACTS
70
"OUT" output contact delay time
1 - 100
1
1
9-10
DELAY TIME
(available on option board)
"OUT" CONTACTS
71
"OUT" output contact hold time
1 - 100
1
1
9-10
HOLD TIME
(available on option board)
LOW SPEED SIGNAL
72
Low-speed signal frequency
0 - Max. Output Freq. 0.1/0.01 Hz
0.0
9-13
OUTPUT FREQ
ACC/DEC COMPLETE
73
Acc/Dec complete detection
0 - Max. Output Freq. 0.1/0.01 Hz
2.5
9-13
DETECT BAND
bandwidth
SPEED REACH MAXIMUM
74
Speed reach high frequency
0 - Max. Output Freq. 0.1/0.01 Hz
0.0
9-13
FREQUENCY
SPEED REACH MINIMUM
75
Speed reach low frequency
0 - Max. Output Freq. 0.1/0.01 Hz
0.0
9-13
FREQUENCY
COMMERCIAL POWER/INV
76
Bypass control
0: Off
-
0
9-13
SWITCHING OUTPUT
1: Automatic
switching upon trip
2: Switching upon
receipt of
switching
signal *
3: Both 1 and 2
above*
COMMERCIAL POWER/INV
77*
Incoming power/inverter
0 - Max Output Freq
0.1/0.01 Hz 60.0 Hz
9-13
SWITCH FREQ
switching frequency
8 - 6
GROUP:TERMINAL SELECTION PARAMETERS
(cont'd)
PARAMETER
DESCRIPTION
LIQUID CRYSTAL DISPLAY
ADJUSTMENT
RANGE
ITEM
NO.
PAGE
NO.
DISPLAY
RESOLUTION
FACTORY
SETTING
Table continued on next page
*Item 77 is available only when Item 76 Adjustment Range option 2 or 3 is selected.
Specifications
Precautions
Wiring
Jumpers
Panel
Keypad
Parameters
Programming
Service
Dimensions
Index
Inspection
Summary of Contents for Adjustable Speed Drive H3
Page 1: ...March 2008 Part 46687 004 ...
Page 2: ......