TOSHIBA
INDUSTRIAL
279
selects application-specific
0: Does nothing
0
9-25
APPLICATIONS
programming (macros)
1: Pump application
2: Fan application
3: Conveyor application
4: Hoist application
5: Textiles application
6: Machine tool application
STANDARD SETTING
280
defaults drive parameters
0: Does nothing
0
9-25
MODE SELECTION
1: 50 Hz setting
2: 60 Hz setting
3: Default drive to factory settings
4: Clear past trips in monitor
5: Store user default settings
6: Default to user default settings
7: Initialize inverter typeform
COMMAND MODE
281
selects START/STOP command
0: Only RS232C input valid
4
9-25
SELECTION
source
1: Terminal input valid
2: Panel input valid
3: RS485 option board
4: Keypad or terminal strip, as set
by LOCAL/REMOTE button.
FREQUENCY MODE
282
selects frequency reference
0: Only RS232C input valid
4
9-25
SELECTION
source
1: Terminal input valid
2: Panel input valid
3: RS485 option board
4: Keypad or terminal strip, as set
by LOCAL/REMOTE button
PANEL OPERATION MODE
* 283
limits keypad's functions
0: Prohibit all key operations
63
9-26
SELECTION
1: Perform reset
2: Perform monitor operations
3: Perform reset, perform monitor
operations
4: Perform emergency stop
5: Perform emergency stop,
perform reset
6: Perform emergency stop,
perform monitor operations
7: Perform emergency stop,
perform monitor operations,
perform reset
8: Perform run/stop operations
9: Perform run/stop operations,
perform reset
10:Perform run/stop operations,
perform monitor operations
11:Perform run/stop operations,
perform monitor operations,
perform reset
12:Perform run/stop operations,
perform emergency stop
13:Perform run/stop operations,
perform emergency stop,
perform reset
14:Perform run/stop operations,
perform emergency stop,
perform monitor operations
8 - 28
GROUP:UTILITY PARAMETERS
PARAMETER
DESCRIPTION
LIQUID CRYSTAL DISPLAY
ITEM
NO.
PAGE
NO.
FACTORY
SETTING
ADJUSTMENT
RANGE
(cont'd)
Table continued on next page
* NOTE: Recycle power after changing ITEM 283,
PANEL OPERATION MODE SELECTION
. ESTOP
from keypad while in remote mode cannot be disabled.
Specifications
Precautions
Wiring
Jumpers
Panel
Keypad
Parameters
Programming
Service
Dimensions
Index
Inspection
Summary of Contents for Adjustable Speed Drive H3