Parameter Explanations (cont'd)
OUTPUT CONTACTS' FUNCTIONS (con't)
Value
Comments
30
Contact closes when dynamic braking resistor is half way or more into its overload as
calculated by the drive based upon the setting in Item 143,
BRAKING RESISTOR VALUE
and
Item 144,
BRAKING RESISTOR POWER RATING
(
GROUP:PROTECTION PARAMETERS
). See
explanation of overload for Value 16 on previous page.
31
Contact closes when dynamic braking resistor is less than half way into its overload as
calculated by the drive based upon the settings in
BRAKING RESISTOR VALUE
and
BRAKING
RESISTOR POWER RATING
. See explanation of overload for Value 17 on previous page.
32
Contact closes when drive is executing an ESTOP
33
Contact closes when drive is not executing an ESTOP
34
Contact closes when drive is executing a retry
35
Contact closes when drive is not executing a retry
36
Contact closes when drive is running a Pattern Run
37
Contact closes when drive is not running a Pattern Run
38
Contact closes when the error signal calculated by the drives PID equals or exceeds the value
programmed into Item 251,
PID DEVIATION UPPER LIMIT
or Item 252,
PID DEVIATION
LOWER LIMIT
(
GROUP:FEEDBACK PARAMETERS
)
39
Contact closes when the error signal calculated by the drives PID does not equal or exceed the
value programmed into
PID DEVIATION UPPER LIMIT
or
PID DEVIATION LOWER LIMIT
40
Contact closes when drive is running at or above 0.01 Hz.
41
Contact closes when drive is not running at or above 0.01 Hz.
42
Contact closes when drive is faulted on a severe fault (not retryable) *
43
Contact closes when drive is not faulted on a severe fault *
44
Contact closes when drive is tripped on a retryable fault *
45
Contact closes when drive is not tripped on a retryable fault *
46
Auto-bypass control. Contact closes to energize coil of output contactor.
47
Opposite logic state of above
48
Auto-bypass control. Contact closes to energize coil of bypass contactor.
49
Opposite logic state of above
50
Contact closes when drives cooling fan(s) is on.
51
Contact closes when drives cooling fan(s) is not on.
52
Contact closes when drive is jogging
53
Contact closes when drive is not jogging
54
Contact closes when drive is getting RUN/STOP command from the keypad
55
Contact closes when drive is not getting RUN/STOP command from the keypad
56
Contact closes when drive run time is greater than or equal to time programmed into Item 174,
CUMULATIVE RUN TIMER ALARM SETTING
(
GROUP:PROTECTION PARAMETERS
)
57
Contact closes when drive run time is not greater than or equal to time programmed into
CUMULATIVE RUN TIMER ALARM SETTING
58
Contact closes when drive trips on a
COMMUNICATION ERROR
59
Contact closes when drive does not have a
COMMUNICATION ERROR
60
Contact changes state when drive goes through 0.0 Hz to change direction. Contact is closed/
open during forward/reverse run. Contact maintains current condition at 0.0 Hz when decel is
complete after a stop command.
61
Contact changes state when drive goes through 0.0 Hz to change direction. Contact is open/
closed during forward/reverse run. Contact maintains current condition at 0.0 Hz when decel is
complete after a stop command.
62
Contact closes when drive has a run command and ST-CC is made
63
Contact closes when drive does not have a run command
* Retryable faults include:
OVERCURRENT(ACCEL)
,
OVERCURRENT(DECEL)
,
OVERCURRENT(RUN)
,
DC OVERCURENT(ACC)
,
DC
OVERCURRENT (DEC)
,
DC OVERCURRENT(RUN)
,
OVERVOLTAGE(ACCEL)
,
OVERVOLTAGE(DECEL)
,
OVERVOLTAGE(RUN)
,
OVERHEAT
,
MOTOR OVERLOAD
,
INVERTER OVERLOAD
,
DBR OVERLOAD TRIP
9 - 12
Specifications