TOSHIBA
9 - 1
SECTION 9: Programming
Note: The H3 will "kick out" of programming mode (return to
OUTPUT FREQUENCY
display) when a
parameter name is displayed for fourteen seconds after the previous parameter has been read and
written.
Press the PRG button to access the H3's programming mode. The drive now displays the first of the
available groups.
The H3 parameters that have related functions are gathered into families called groups.
Use the up/down arrows to scroll through the available group list.
Groups
With factory default programming, the H3 displays only three groups:
GROUP: PARAMETERS CHANGED FROM FACTORY DEFAULT
GROUP: FUNDAMENTAL PARAMETERS #1
GROUP: UTILITY PARAMETERS
The following is a list of all H3 groups:
GROUP: PARAMETERS CHANGED FROM FACTORY DEFAULT
GROUP: FUNDAMENTAL PARAMETERS #1
GROUP: FUNDAMENTAL PARAMETERS #2
GROUP: PANEL CONTROL PARAMETERS
GROUP: SPECIAL CONTROL PARAMETERS
GROUP: TERMINAL SELECTION PARAMETERS
GROUP: FREQUENCY SETTING PARAMETERS
GROUP: PROTECTION PARAMETERS
GROUP: PATTERN RUN CONTROL PARAMETERS
GROUP: FEEDBACK PARAMETERS
GROUP: COMMUNICATION SETTING PARAMETERS
GROUP: INDUSTRIAL APPLICATION PARAMETERS (PUMP)
GROUP: INDUSTRIAL APPLICATION PARAMETERS (FAN)
GROUP: INDUSTRIAL APPLICATION PARAMETERS (CONVEYOR)
GROUP: INDUSTRIAL APPLICATION PARAMETERS (HOIST)
GROUP: INDUSTRIAL APPLICATION PARAMETERS (TEXTILES)
GROUP: INDUSTRIAL APPLICATION PARAMETERS (MACHINE TOOLS)
GROUP: AM/FM TERMINAL ADJUSTMENT PARAMETERS
GROUP: UTILITY PARAMETERS
GROUP: MOTOR PARAMETERS
Programming Example 1
Objective: Set
ACCELERATION TIME #1
to 23.4 seconds.
Step 1:
ACCELERATION TIME #1
(Item 10) is in
GROUP: FUNDAMENTAL PARAMETERS #1
,
so press the PRG key and use the up/down arrows to scroll through the group list until
GROUP: FUNDAMENTAL PARAMETERS #1
is displayed.
Step 2: Press the READ/WRITE key. Drive will then display
MAXIMUM OUTPUT FREQUENCY
(Item 1), because
MAXIMUM OUTPUT FREQUENCY
is the first parameter in
GROUP: FUNDAMENTAL PARAMETERS #1
.
Step 3: Use the up/down arrows to scroll through the parameters in
GROUP: FUNDAMENTAL
PARAMETERS #1
until the desired parameter (in this case,
ACCELERATION TIME #1
),
is displayed.
Step 4: Press the READ/WRITE key. Drive will display the value stored in this parameter.
Step 5: Adjust displayed value with up/down arrow keys. Press READ/WRITE when finished.
Drive flashes
WRT
to confirm entry.
Step 6: Use up/down arrows to select another parameter in this group, or press PRG to exit.
Summary of Contents for Adjustable Speed Drive H3
Page 1: ...March 2008 Part 46687 004 ...
Page 2: ......