15
1600ep Series instruction manual
UPS
Specifications
STANdArd MOdeLS: 3.6
kVA-RoHS; 3.6kVA; 6kVA; 8kVA
Unit (Capacity)
3.6 kVa-rohS
(3.1 kw)
1
3.6 kVa (3.1 kw)
1
6 kVa (5.1 kw)
1
8 kVa (6.8 kw)
1
general
topology
true on-line
Certifications
Ul, CUl, iSo 9001, nema/pe1-1993
input Characteristics
input Voltage
Single-phase, 208/240 Vac, -30% – +10%
input Frequency
45 – 65 hz (auto-sensing)
input Capacity
3.6 kVa
6.0 kVa
8.0 kVa
input power Factor
> 0.95 for all loads
Current thD (linear load)
< 5% total harmonic distortion
included aC input breaker
rating
30 a/277 V
50 a/277 V
60 a/277 V
battery Characteristics
battery type
Valve regulated lead acid, Flame retardant
backup time, fully charged
@ 0.7 power factor, 77 °F
8 min.
minimum
2
14 min.
minimum
2
7 min.
minimum
2
backup time, fully charged
@ 0.85 power factor, 77 °F
7 min.
minimum
2
10 min.
minimum
2
7 min.
minimum
2
recharge time
24 hr. (full), 12 hr. (90%) for internal batteries only
3
battery Voltage (nominal)
144 Vdc
216 Vdc
216 Vdc
288 Vdc
output Characteristics
output Voltage
Single-phase, 240/208/120 V
output Voltage regulation
± 3%
output Frequency
±0.5 hz/1 hz/1.5 hz (factory or authorized service center selectable only)
aUto/man Frequency
Factory or authorized service center selectable only
Voltage thD
< 3% for linear load; < 6% for non-linear load
Common-mode noise
< 0.5 Vrms
rated load power Factor
0.85 (0.6 – 1.0) lagging
Efficiency (ac-dc-ac)
> than 83% (without battery charge)
Voltage transient
< ±8% (load of 0 – 100 %)
rated output Current (rms)
15 a
25 a
33.3 a
max. peak output Current
45 a
75 a
100 a
inverter overload Capacity
125% for 30 sec./150% for 10 sec.
bypass overload Capacity
125% for 10 min./1000% for 1 cycle
Crest Factor
3.0
Input/output figures rated for 240 volts. Output ratings given for 0.85PF are only valid when the
input voltage is
greater than 204 volts; otherwise, ratings given for 0.70pF are applicable.
battery backup time may vary depending on the operating conditions and ambient temperature at the installation site.
an initial charge time of 24 hrs. is necessary to obtain proper battery performance level before unit is placed in operation.
1.
2.
3.
Summary of Contents for 1600EP Series
Page 2: ......
Page 6: ...1600EP Series Instruction Manual This page intentionally left blank ...
Page 18: ...10 1600EP Series Instruction Manual ...
Page 57: ...49 1600EP Series Instruction Manual External Layout for 3 6 kVA RoHS 3 6 kVA and 6 kVA units ...
Page 62: ...54 1600EP Series Instruction Manual ...
Page 63: ......