BUILT-IN UPS FAULT PROTECTION FUNCTIONS (CONT’D)
protection item
internal overheat
DC Circuit overvoltage
DC Circuit overcurrent
lCD message
OVERHEAT
DC-OV
DC-OC
Cause
Fan failure;
high ambient temperature
Chopper malfunction
inverter/chopper fault
operation mode
after Fault
Shutdown – no output
bypass operation – Chopper and inverter are stopped
inverter ol – transfer to bypass
audible alarm
yes – Continuous buzzer
Visible alarm
red Fault leD on
relay Contact
alarm
Fault relay closed
bypass relay closed
auto-retransfer
no