1600ep Series instruction manual
STANdArd MOdeLS: 3.6
kVA-RoHS; 3.6kVA; 6kVA; 8kVA (CONT’D)
Unit (Capacity)
3.6 kVa-rohS
(3.1 kw)
1
3.6 kVa (3.1 kw)
1
6 kVa (5.1 kw)
1
8 kVa (6.8 kw)
1
environment
operating temperature
59 – 77 °F (15 – 25 °C)
recommended
60 hz
50 hz
32 – 104 °F (0 – 40 °C)
32 – 91 °F (0 – 33 °C)
Storage temperature
-4 – 104 °F (-20 – 40 °C)
installation area
to be installed in a well ventilated area free of airborne dust,
metal particles or flammable gas, allow at least 4 inches on all sides
operating humidity
30 – 90% non-condensing
altitude
< 3300 ft. (1000 m) above sea level
2
acoustical noise
50 db (a) maximum @ 1 meter from front panel
heat generation
1588 btU/hr
1588 btU/hr
2610 btU/hr
3482 btU/hr
operation Diagnosis
battery Check
Performed on start up, by schedule, on-demand (user configurable)
input oV protection
Standard
battery lifetime
UpS calculates battery replacement time
based upon battery ambient temperature (lCD display, leD and beeps)
internal temperature
UpS gives indication of internal temperature, alarm when high temp
event Data Storage
64 – Supply mode, 32 – backup, 16 – Faults
applications
Switches
generator compatibility
bypass Switch
bypass Disable
Static switch < ¼ cycle (50 hz – 5 ms/60 hz – 4.16 ms)
automatic retransfer
Factory or authorized service center selectable only
User interface
provided – Can be disabled from front panel
real time Clock
Schedule operation
Standard – minimum 3 days memory backup during power loss
rUn/Stop Disable
Schedule on/oFF operation of UpS using communication software
autostart
UpS has option for UpS to start automatically when aC is applied
remote on/oFF
Standard – external terminal
leD Display
4 leD’s indicating input/output condition, warning and battery operation
lCD Screen
16 characters x 2 lines
UpS operation: 6 Keys
run/Stop, Set/monitor, Shift/Select, Del/page Down, reset/page Up
buzzer Volume
Selectable by keypad – low, high, mute
power Connections
Standard – hard wire
emergency power off
Standard – terminal contacts only
remote Contacts
Standard (inV, byp, batt, lb, aC, Flt)
rS232 aSCii interface
Standard
Input/output figures rated for 240 volts. Output ratings given for 0.85PF are only valid when the
input voltage is
greater than 204 volts; otherwise, ratings given for 0.70pF are applicable.
at 6600 ft (2000 m) above sea level, output capacity should be derated by 3%
1.
2.
Summary of Contents for 1600EP Series
Page 2: ......
Page 6: ...1600EP Series Instruction Manual This page intentionally left blank ...
Page 18: ...10 1600EP Series Instruction Manual ...
Page 57: ...49 1600EP Series Instruction Manual External Layout for 3 6 kVA RoHS 3 6 kVA and 6 kVA units ...
Page 62: ...54 1600EP Series Instruction Manual ...
Page 63: ......