21
1600ep Series instruction manual
Operating the UPS
Battery Backup Time and Discharge Process
the UpS batteries provide about 5-7 minutes of back-up time depending on the 1600ep unit kVa rating.
these times are valid when the unit is operating under full load and at the rated power factor. the exact
length of these times will depend on the UpS model used, condition of the batteries, amount and type of
load, temperature and other variables. See battery backup time in ‘Standard Specifications’ beginning on
page
s 15-20.
the following illustration graphically shows the battery discharge process at full load conditions.
Battery Low Voltage Tolerances
excessive discharge will cause the UpS battery voltage to drop. the chart shown below lists the voltage
level at which each UpS low-voltage alarm will sound and at what level the low-voltage condition will
cause the unit to automatically shut down.
UpS Capacity
3.6 kVa-
rohS
3.6 kVa
6 kVa
8 kVa
10 kVa
14 kVa
18 kVa
22 kVa
nominal voltage (Vnom)
144 Vdc
216 Vdc 216 Vdc 288 Vdc 288 Vdc 288 Vdc 288 Vdc 288 Vdc
alarm voltage (Vlow)
130 Vdc
192 Vdc 192 Vdc 246 Vdc 246 Vdc 246 Vdc 246 Vdc 246 Vdc
Shutdown voltage (Vmin)
114 Vdc
170 Vdc 170 Vdc 227 Vdc 227 Vdc 227 Vdc 227 Vdc 227 Vdc
BATTERY CAPACITY
SHUTDOWN
I
MAx
I
MIN
V
NOM
V
LOW
V
MIN
100%
20% 0%
CURRENT VOLTAGE
Summary of Contents for 1600EP Series
Page 2: ......
Page 6: ...1600EP Series Instruction Manual This page intentionally left blank ...
Page 18: ...10 1600EP Series Instruction Manual ...
Page 57: ...49 1600EP Series Instruction Manual External Layout for 3 6 kVA RoHS 3 6 kVA and 6 kVA units ...
Page 62: ...54 1600EP Series Instruction Manual ...
Page 63: ......