Inspection/Storage/Disposal
Inspection
Upon receipt of the UpS, an inspection for shipping damage should be performed. Use caution when
removing the unit from the pallet. refer to labels or documentation attached to packing material.
Unpacking
Check the unit for loose, broken, bent or otherwise damaged parts. if damage has occurred during
shipping, keep all original crating and packing materials for return to the shipping agent. the warranty
does not apply to damage incurred during shipping. ensure that the rated capacity and the model number
specified on the nameplate conform to the order specifications.
Storage
During periods of non-use, the following guidelines are recommended for storage.
Storage Preparation
power up the UpS and allow it to operate with no load for 24 hours to fully charge the
batteries.
Stop the unit
(see Stop operation on page 25).
place the mCCb switch
(see page 47 for location)
in the off position.
Storing Conditions
For best results, store the UpS in the original shipping container and place on a wood
or metal pallet.
Storage temperature: -4 – 104 °F (-20 – 40 °C).
the optimum storage temperature is 70 °F (21 °C). a higher ambient temperature will
require recharging more frequently during storage.
avoid storage locations that:
are subject to extreme temperature changes or high humidity.
are subject to high levels of dust or metal particles.
are subject to excessive vibration.
Have inclined floor surfaces.
Storage Maintenance
if stored at an ambient temperature less than 68 °F (20 °C), recharge the batteries
every 9 months.
if stored at an ambient temperature of 68 – 86 °F (20 – 30 °C), recharge the batteries
every 6 months.
if stored at an ambient temperature of 86 – 104 °F (30 – 40 °C), recharge the batteries
every 3 months.
Disposal
please contact your local or state environmental agency for details on disposal of electrical components
and packaging in your particular area.
It is illegal to dump lead-acid batteries in landfills or dispose of improperly.
please help our earth by contacting the environmental protection agencies in your area, the battery
manufacturer, or call toshiba toll-free at (877) 867-8773 for more information about recycling.
1.
2.
3.
•
•
•
•
•
•
•
•
•
•
Summary of Contents for 1600EP Series
Page 2: ......
Page 6: ...1600EP Series Instruction Manual This page intentionally left blank ...
Page 18: ...10 1600EP Series Instruction Manual ...
Page 57: ...49 1600EP Series Instruction Manual External Layout for 3 6 kVA RoHS 3 6 kVA and 6 kVA units ...
Page 62: ...54 1600EP Series Instruction Manual ...
Page 63: ......