20
Character
Description
Initial value
Setting range
Main control sensitivity
1
C
<Thermocouple >
0 to 199
C
<resistance temperature detector>
0.0 to 199.9
C
Main control off-point
position
0
C
<Thermocouple >
0 to 199
C
<Resistance temperature detector>
0.0 to 199.9
C
Main control protection off
Timer
0minutes
0 to 99 minutes
Sub-control sensitivity
1
C
<
Thermocouple
>
0 to 199
C
<
Resistance temperature detector
>
0 to 199.9
C
Sub-control off-point
position
0
C
<Thermocouple >
0 to 199
C
<Resistance temperature detector>
0 to 199.9
C
Sub-control protection off
Timer
0minutes
0 to 99 minutes
Dead band
0
C
<Thermocouple>
0 to 199
C
<Resistance temperature detector>
0 to 199.9
C
Event temperature setting mode parameters
Character
Description
Initial value
Setting range
Event Output 1 lower and
upper limits
Upper limit: 0
Lower limit: 0
<Thermocouple>
-1999 to +9999
C
<Resistance temperature detector>
-199.9 to +999.9
C
Event Output 2 lower and
upper limits
Upper limit: 0
Lower limit: 0
<Thermocouple>
-1999 to +9999
C
<Resistance temperature detector>
-199.9 to +999.9
C