19
Control setting
mode parameters
Character
Description
Initial value
Setting range
Control type
0
No.
Main control
Sub-control
0
PID
N/A
1
ON/OFF
N/A
2
PID
PID
3
PID
ON/OFF
4
ON/OFF
ON/OFF
OUT1 function
0
0:Main output
1:Sub-output
2:Transmission output(for analog output)
OUT2 function
1
0:Main output
1:Sub-output
2:Run Signal Output / Event Output
Main control proportional
band low temperature
3.0%
0.1 to 200.0 %
Main control proportional
band middle temperature
3.0%
Main control proportional
band high temperature
3.0%
Integration time
low temperature
0 seconds
0 to 3600 seconds
Integration time
middle temperature
0 seconds
Integration time
high temperature
0 seconds
Differentiation time
low temperature
0 seconds
0 to 3600 seconds
Differentiation time
middle temperature
0 seconds
Differentiation time
high temperature
0 seconds
Auto Tuning execution
temperature for low
temperature control zone
0
C
As per the PID range setting
Auto Tuning execution
temperature for middle
temperature control zone
0
C
Auto Tuning execution
temperature for high
temperature control zone
0
C
PID range midpoint 1
0
C
Between minimum and maximum in the
temperature setting range -50°C
PID range midpoint 2
0
C
Intermediate point 1 to the maximum in the
temperature setting range
Sub-control proportional
band low temperature
3.0%
0.1 to 200.0 %
Sub-control proportional
band middle temperature
3.0%
Sub-control proportional
band high temperature
3.0%