6.3 Parameter description
Program setting mode parameters
Character
Description
Initial value
Setting range
□
Set a step
□
temperature
0
Setting range
(K: 0 to 1300
C/J: 0 to 800
C/R: 0 to 1700
C/
T: 0 to 1300
C/N: 0 to 800
C/S: 0 to 1700
C/
B: 0 to 1800
C /S: 0 to 1700
C/Pt100Ω: 0.0 to 500.0
C)
□
Set a step
□
time
0.00
0 to 99 hours 59 minutes
Common parameter setting mode parameters
Character
Description
Initial value
Setting range
Set the PV correction zero
point
0
-199 to +199°C
Set the PV correction gain 1.00
0.50 to 2.00 times
Forward/reverse
switchover
2
1: Forward action (cooling)/2: reverse action (heating)
Sensor switchover
1
1: K thermocouple/2: J thermocouple/3: R thermocouple
4: T thermocouple/5: N thermocouple/6: S thermocouple
7: B thermocouple/8: Resistance temperature detector
SV limiter upper limit
1200
<Thermocouple >
SLL + 50°C to setting range upper limit
<
Resistance temperature detector
>
SLL + 50.0°C to setting range upper limit
SV limiter lower limit
0
<Thermocouple >
setting range lower limit to SLH-50
C
<
Resistance temperature detector
>
setting range lower limit to SLH-50.0
C
Set the number of patterns 8
1 to 15 patterns
Select PV/SV start
PV
PV1: PV start 1 / PV2: PV start 2 / SV: SV start
Set an SV start
temperature
0
Lower limit to upper limit of the temperature setting range
Main control proportional
period
R (relay output): 20
S (SSR output): 2
1 to 120 seconds
Sub-control
proportional period
R (relay output): 20
S (SSR output): 2
1 to 120 seconds
Wait zone
0
<Thermocouple >
0 to 100
C
<
Resistance temperature detector
>
0.0 to 100.0
C
Wait time
0.00
0 to 99 hours 59 minutes
Time signal / Event
Output 1 type
00
(Time signal)
0: Nil (Time signal/Run Signal
Output)
1: Deviation upper and lower limit
2: Deviation upper limit
3: Deviation lower limit
4: Deviation upper and lower limit
range
5: Absolute value upper and lower
limit
6: Absolute value upper limit
7: Absolute value lower limit
8: Absolute value upper and lower
limit range
0: No additional functions
1: Output held
2: Standby sequence
3: Output held + standby
sequence
Run signal Output / Event
Output 2 type
00
(Run Signal
Output)
Event Output 1 sensitivity 1
<Thermocouple >
0 to 199°C
<Resistance temperature detector>
0.0 to 199.9°C
Event Output 2 sensitivity 1
Time signal ON time
0.00
0 to 99 hours 59 minutes
Time signal OFF time
0.00
0 to 99 hours 59 minutes