![Toa VX-3308WM Operating Instructions Manual Download Page 53](http://html.mh-extra.com/html/toa/vx-3308wm/vx-3308wm_operating-instructions-manual_1123506053.webp)
Chapter 2
INDICATOR STATUS OF REMOTE MICROPHONES
2-
40
[When assigned to the function key]
Emergency Acknowledge Indicator
Emergency operation enable/disable indicator
Function key
(Emergency Acknowledge key)
Indicator meanings are as follows:
*
1
All operations related to the emergency broadcasts such as Emergency broadcast pattern start/stop, Emergency
sequence phase shift, and Emergency reset.
*
2
It is so set by the VX-3000 Setting Software that Emergency operation cannot be performed until the emergency
acknowledge key is pressed once the emergency broadcast pattern has been activated.
*
3
It is so set by the VX-3000 Setting Software that Emergency operation can be performed without pressing the emergency
acknowledge key once the emergency broadcast pattern has been activated.
Indicator
Status
Emergency operation*
1
Unlit
enable/disable indicator
Meaning
When set to EMG enable operation ON*
2
:
Emergency operation from this remote microphone is
disabled.
When set to EMG operation OFF*
3
(Constantly unlit)
Lights green
Emergency Acknowledge
Indicator
Unlit
When set to EMG enable operation ON*
2
:
Emergency operation*
1
from this remote microphone is
enabled.
When the system is not in emergency mode
Flashes red
When the system is in emergency mode and emergency
acknowledge has not been received by this remote
microphone.
Lights red
When the system is in emergency mode and emergency
acknowledge has been received by this remote microphone.