![Toa VX-3308WM Operating Instructions Manual Download Page 15](http://html.mh-extra.com/html/toa/vx-3308wm/vx-3308wm_operating-instructions-manual_1123506015.webp)
Chapter 2
INDICATOR STATUS OF REMOTE MICROPHONES
2-
2
1. RM-200SF FIREMAN’S MICROPHONE AND RM-320F REMOTE
MICROPHONE EXTENSION
1.1. Indicator State at the Time of Zone Selection
When a zone selection (pattern or individual) function has been assigned to a function key, the 2 indicators to
the left of the key indicate its zone selection and broadcast status.
Note
For instructions on assigning functions to function keys, see the separate Setting Software Instructions, "EVENT
SETTINGS."
Zone Selection Indicator
Broadcast Status Indicator
Function key (Broadcast zone selection key)
Indicator meanings are as follows:
Indicator
Status
Meaning
Zone Selection Indicator
Unlit
No zone selected
Lights green
Zone selected
Broadcast Status Indicator
Unlit
Zones assigned to this Broadcast Zone Selection key not in
use or BGM broadcast in progress
Flashes green
A part of zones or the entire zone assigned to this Broadcast
Zone Selection key is occupied by a broadcast from another
device (secondary Remote Microphone. or general EV
message), or a part of zones is engaged by a broadcast from
the primary Remote Microphone (RM-200SF).
Lights yellow
All the zones selected by this Broadcast Zone Selection
key on the primary Remote Microphone are engaged by a
broadcast from the primary Remote Microphone.
Flashes yellow
All the zones assigned to this Broadcast Zone Selection key
are engaged by a broadcast from the Secondary Emergency
Remote Microphone.
Lights red
All the zones assigned to this Broadcast Zone Selection key
are engaged by an evacuation message.
Flashes red
All the zones assigned to this Broadcast Zone Selection key
are engaged by an alert message.
Lights green
All the zones assigned to this Broadcast Zone Selection key
are engaged by a restoration message.