44
Smart valve positioner
TS800/TS805 Series
tissin
DSP NORM
Display the valve opening value on LCD in direct/reverse direction.
Mode
Description
DSP NORM
Displayed 0% on LCD when the valve is 0%, and
displayed 100% on LCD when the valve is 100%.
DSP REVE
Displayed 100% on LCD when the valve is 0%, and
displayed 0% on LCD when the valve is 100%.
Factory setting
DSP NORM
6.7.4 INFOMATN
You can find the following information through Submenu.
Submenu
Description
FIRM VER
Display firmware version of the product.
DEVI REV
Display the version of device.
HART VER
Display the version of HART communication.
POLL ADD
Display Polling address of the device in HART communication.
TRAVEL K
Display the accumulated total travel distance of the valve after the
positioner has been used. (Unit: K%)
One full travel distance from full close to full open means 100% = 0.001K%
For example, if the travel value is 1K%, this means that the valve has
moved 1000 stroke percentages.
OP TIME
Display the time that takes from the valve fully close to fully open during
Auto calibration.
Unit : Second
CL TIME
Display the time that takes from the valve fully open to fully close during
Auto calibration.
Unit : Second
TEMPERAT
Check the current ambient temperature of the positioner through the built-in
temperature sensor.
TEMP MAX
Display the recorded highest ambient temperature value after using the
product.
TEMP MIN
Display the recorded lowest ambient temperature value after using the
product.