6.7 Submenu Description
The following is a detailed description of Main parameter menu’s Submenu.
Press <
ENTER
> button in Main parameter menu to enter Submenu.
Use <
UP
> and <
DOWN
> button to move between Submenu.
6.7.1 TUNNING
Submenu
Description
AUTO RUN
Run Auto calibration.
Executable from any input signal between 4 and 20 mA.
It takes 1~3 minutes, depending on the valve size.
AM
Select Auto calibration mode.
Mode
Description
AM FULL
Set all parameter values again.
AM BIAS
Only reset the motor reference value, but the
other parameter values are not modified.
AM PIDb
Only reset PID value, but the other parameter
values are not modified.
AM ZEb R
Only reset End point and Zero point of the valve,
but the other parameter values are not modified.
Factory setting
AM FULL
TbL
Set the sensitivity of product.
The setting value can be changed when hunting occurs due to a
large friction of the valve stem or a small actuator size.
TbL 1 HS
When you want to increase the sensitivity.
For example, when the actuator size is small.
TbL 2 NS
Normal mode.
TbL 3 LS
When you want to lower the sensitivity.
For example, when hunting occurs due to the
high friction of the valve stem.
TbL 4 LLS
When the actuator size is very large.
Factory setting
TbL 2 NS
VAL OPCL
Regardless of the current signal, it performs the function of opening
and closing the valve with <
UP
> or <
DOWN
> button manually.
VAL ZERO
Reset ZERO point of the valve manually.
Input 4mA current, press <
UP
> and <
DOWN
> button to change the
valve position, and press <
ENTER
>button to save the current valve
position, then the positioner recognizes the current position as valve
ZERO point.