38
Smart valve positioner
TS800/TS805 Series
tissin
VAL END
Reset END point of the valve manually.
Input 20mA current, press <
UP
> and <
DOWN
> button to change the
valve position, and press <
ENTER
>button to save the current valve
position, then the positioner recognizes the current position as valve
END point.
OUT ZERO
Reset ZERO point of the feedback signal manually.
Input
4mA
current signal, valve reaches Zero position, after press
<
UP
> or <
DOWN
> button to adjust the value, until the 4mA feedback
signal is output, and then press
<
ENTER
>button to save.
NOTICE
Please reset
OUT ZERO
setting after installing feedback module.
OUT END
Reset END point of the feedback signal manually.
Input
20mA
current signal, valve reaches end position, after press
<
UP
> or <
DOWN
> button to adjust the value, until the 20mA
feedback signal is output, and then press
<
ENTER
> button to save.
NOTICE
Please reset
OUT END
setting after installing feedback module.
IN ZERO
Reset ZERO value of input signal manually.
If <
MAIN IN%
> and <
MAIN mA
> displayed at Main menu differ from
the actual input signal, conduct the commands of this menu.
Input 4mA current at this menu and press <
ENTER
> button twice to
save.
NOTICE
After replacing the main board or conduct
program initialization
,
please reset
IN ZERO
setting.
IN END
Reset END value of input signal manually.
If <
MAIN IN%>
and <
MAIN mA
> displayed in Main menu differ from
the actual input signal, conduct the commands of this menu.
Input
20mA
current at this menu and press <
ENTER
> button twice to
save.
NOTICE
After replacing the main board or
conduct program initialization
,
please reset
IN END
setting.
BIAS25
The reference value of the motor when valve stroke is 25%.
It is set automatically during Auto calibration, so please do not modify
this parameter value manually.
BIAS75
The reference value of the motor when valve stroke is 75%.
It is set automatically during Auto calibration, so please do not modify
this parameter value manually.