24
Smart valve positioner
TS800/TS805 Series
tissin
3.5.4 How to adjust limit switch cam
①
Dome indicator
②
Switch
③
Fixing bolt
④
Phillips
screwdriver
The cam position is set at the factory. If you want to change the cam position, please follow the
steps below.
①
Open the cover and separate the dome indicator by referring to the above figure.
②
Loosen the fixing bolt slightly with a Phillips screwdriver, but do not separate it.
③
Adjust cam 3 and 4 by referring to the following figure below, and adjust the angle so that
the switch operates at the position you want.
④
After adjusting the angle, fasten the fixing bolt tightly.
Mechanical switch
Proximity switch
①
Micro switch 1
②
Micro switch 2
③
Operating cam 1
④
Operating cam 2
⑤
Fixing screw
①
Proximity switch 1
②
Proximity switch 2
③
Operating cam1
④
Operating cam 2
⑤
Fixing screw