42
Smart valve positioner
TS800/TS805 Series
tissin
FORCE CL
When the input current signal is lower than the set value, the valve is
forced to close.
When the valve is closed, residual pressure in the actuator chamber
can be completely released.
Range
0~100%
Factory setting
0.3%
Note
When the value set to 0%, this function is
not applied.
DAMP
This function controls the operating speed of the valve.
The higher the set value, the slower the operating speed of the valve.
With this function, hunting problem in small actuator can be solved.
Range
0~500
Factory setting
0
Note
When the value set to 0, this function is not
applied.
SPLIT ZER
Set Zero point of the signal
value during the split range control.
For example, if the set value is
50%, 12mA corresponds to 0%
of the valve opening as shown
on the right figure .
Range
0~100.0%
Factory setting
0.0%
SPLIT END
Set End point of the signal
value during the split range control.
For example, if the set value is
50%, 12mA corresponds to 100%
of the valve opening as shown
on the right figure .
Range
0~100.0%
Factory setting
100.0%