Service settings manual
41
Para-
meter
Function
Parameter description
Setting range
Default
value
F2.7
SENSOR FOR
THERMOSTATIC
OPERATION
Selection of sensor for thermostatic operation.
1- T1 2- T2
3- T3 4- T4
5- T5 6- T6
4
F2.8
THERMOSTAT
HYSTERESIS
Hysteresis for thermostatic operation.
1 ÷ 30 K
4
F2.9
AUXILIARY HEAT
SOURCE - DE-
LAYED ACTIVATI-
ON
Selection if auxiliary heat source should activate immediately or
with delay if the collectors have trend and tendency to warm the
water to requested temperature. Delay time is considered as a
time in which the collectors should warm the water to requested
temperature. Auxiliary heat source will activate immediately if
collectors don't have trend and tendency to warm the water to
requested temperature in setted delayed activation time.
0- NO DELAY
1 ÷ 1440 min-
DELAY
0
F2.10
AUXILIARY HEAT
SOURCE - STAND-
BY AT MIN. TEM-
PERATURE
Selection if auxiliary heat source should permanently heat the
water to min. temperature.
0- NO
1- YES, BY TIME
PR.
2- ALWAYS
0
F2.11
DIFFERENTIAL
THERMOSTAT
Selection if programmed output should operate as a differential
thermostat.
0- NO
1- YES
2- YES, INVER-
TED
0
F2.12
HEAT SOURCE
SENSOR FOR
DIFF. THERMO-
STAT
Selection of heat source sensor (higher temperature) for diffe-
rential thermostat.
1- T1 2- T2
3- T3 4- T4
5- T5 6- T6
3
F2.13
HEAT SINK SEN-
SOR FOR DIFF.
THERMOSTAT
Selection of heat sink sensor (lower temperature) for differential
thermostat.
1- T1 2- T2
3- T3 4- T4
5- T5 6- T6
4
F2.14
SWITCH- ON DIF-
FERENCE FOR
DIFFERENTIAL
THERMOSTAT
Switch -on difference setting for differential thermostat.
4 ÷ 30 °C
8
F2.15
SWITCH- OFF
DIFFERENCE FOR
DIFFERENTIAL
THERMOSTAT
Switch -off difference setting for differential thermostat.
1 ÷ 20 °C
3
F2.16
CIRCULATION ON
OUTPUT
Selection if output should be used for hot water circulation and
the way it should operate.
1- circulation with pump running and standby time
2- circulation is activated with flow switch on terminal T3 and is
running for setted running time
3- circulation is activated with flow switch on terminal T4 and is
running for setted running time
4- circulation is activated with flow switch on terminal T5 and is
running for setted running time
5- circulation is activated with flow switch on terminal T6 and is
running for setted running time
0- NO
1- YES, RUN/
STANDBY TIME
2- YES, T3
3- YES, T4
4- YES, T5
5- YES, T6
0
A1343_3
MJ/OD
06/2018
Summary of Contents for SGC36HV
Page 2: ...A1343_3 MJ OD 06 2018 ...
Page 4: ...A1343_3 MJ OD 06 2018 ...
Page 180: ...NOTES NOTIZEN POZNÁMKY 180 A1343_3 MJ OD 06 2018 ...
Page 181: ...NOTES NOTIZEN POZNÁMKY 181 A1343_3 MJ OD 06 2018 ...
Page 182: ...NOTES NOTIZEN POZNÁMKY 182 A1343_3 MJ OD 06 2018 ...
Page 183: ...A1343_3 MJ OD 06 2018 ...