Service settings manual
34
Table with description of parameters
:
Para-
meter
Function
Parameter description
Setting range Default-
value
S3.1
SOLAR PUMP R2 OPERATI-
ON MODE
You can set the operation mode of the R2 pump with a set-
ting.
0- ON/OFF mode is used exclusively for control of classic
pumps without speed control
1- RPM mode is used exclusively for speed control of classic
pumps
2- PWM mode is used exclusively for speed control of high
efficiency solar pumps with external PWM control signal
3- PWM, INVERTED mode is used exclusively for speed
control of high efficiency heating pumps with external PWM
control signal
4- 0-10 V mode is used exclusively for speed control of high
efficiency solar pumps with external analogue control signal
5- 10-0 V mode is used exclusively for speed control of high
efficiency heating pumps with external analogue control
signal
0- ON/OFF
1- RPM
2- PWM
3- PWM,
INVERT.
4- 0-10 V
5- 10-0 V
0
S3.2
MIN. SPEED (RPM) FOR
SOLAR PUMP R2
Minimum speed rate (RPM) for the R2 pump is set. The
setting is only valid for the speed control of a classic circulati-
on pump.
1- 40 %
2- 55 %
3- 70 %
1
S3.3
TIME OF MAX. SPEED FOR
SOLAR PUMP R2
When the differential condition is fulfilled, the R2 runs at full
speed for a setted time.
5 ÷ 300 s
20
S3.4
MIN. PWM / 0-10 V FOR
SOLAR PUMP R2
Minimum speed rate for the R2 pump is set. This setting is
only valid for the speed control of high efficiency circulation
pump.
20 ÷ 50 %
20
S3.5
MAX. PWM / 0-10 V FOR
SOLAR PUMP R2
Maximum rotation rate for the R2 pump is set. This setting is
only valid for the speed control of high efficiency circulation
pump.
60 ÷100 %
100
S3.6 SWITCH-OFF PWM / 0-10 V
FOR SOLAR PUMP R2
A control signal is set, where the R2 pump will be switch-off.
This setting is only valid for high efficiency circulation pumps
with control line break detection.
0 ÷ 10 %
5
S3.7 SOLAR PUMP R3 OPERATI-
ON MODE
You can set the operation mode of the R3 pump with a set-
ting.
0- ON/OFF mode is used exclusively for control of classic
pumps without speed control
1- RPM mode is used exclusively for speed control of classic
pumps
2- PWM mode is used exclusively for speed control of high
efficiency solar pumps with external PWM control signal
3- PWM, INVERTED mode is used exclusively for speed
control of high efficiency heating pumps with external PWM
control signal
4- 0-10 V mode is used exclusively for speed control of high
efficiency solar pumps with external analogue control signal
5- 10-0 V mode is used exclusively for speed control of high
efficiency heating pumps with external analogue control
signal
0- ON/OFF
1- RPM
2- PWM
3- PWM,
INVERT.
4- 0-10 V
5- 10-0 V
0
A1343_3
MJ/OD
06/2018
Summary of Contents for SGC36HV
Page 2: ...A1343_3 MJ OD 06 2018 ...
Page 4: ...A1343_3 MJ OD 06 2018 ...
Page 180: ...NOTES NOTIZEN POZNÁMKY 180 A1343_3 MJ OD 06 2018 ...
Page 181: ...NOTES NOTIZEN POZNÁMKY 181 A1343_3 MJ OD 06 2018 ...
Page 182: ...NOTES NOTIZEN POZNÁMKY 182 A1343_3 MJ OD 06 2018 ...
Page 183: ...A1343_3 MJ OD 06 2018 ...