11.3.7
Autotune at Setpoint – Heat/Cool
It is sometimes necessary to tune at the actual setpoint being used. This is allowable in 3200 series controllers and the
sequence of operation is described below.
Period
Action
A
Start of Autotune.
A test is done at the start of autotune to establish the conditions for a tune at setpoint.
The conditions are that the SP must remain within 0.3% of the range of the controller if ‘PB.UNt’ is set to
‘Percent’. If ‘PB.UNT’ is set to ‘Eng’ then the SP must remain 1 engineering unit (1 in 1000). Range is
defined as ‘RNG.HI’ – ‘RNG.LO’ for process inputs or the range defined in section 0 for temperature inputs.
A to B
The output is frozen at the current value for one minute and the conditions are continuously monitored during
this period. If the conditions are met during this period autotune at setpoint is initiated at B. If at any time
during this period the PV drifts outside the condition limits a tune at setpoint is abandoned. Tuning is then
resumed as a tune from above or below setpoint depending on which way the PV has drifted.
Since the loop is already at setpoint there is no need to calculate a Tune Control Setpoint – the loop is forced to
oscillate around the Target Setpoint
C to G
Initiate oscillation - the process is forced to oscillate by switching the output between the output limits. From
this the period of oscillation and the peak to peak response is measured. PID terms are calculated
G to H
An extra heat stage is provided and all heating and cooling power is turned off at H allowing the plant to respond
naturally.
Measurements made during this period allow the relative cool gain ‘R2G’ to be calculated.
I
Autotune is turned off and the process is allowed to control at the target setpoint using the new control terms.
For a tune at setpoint autotune does not calculate cutback since there was no initial start up response to the application
of heating or cooling. The exception is that the cutback values will never be returned less than 1.6*PB.
Hysteresis
A – B =1 min
A - Start of
Autotune
I
C
D
E
F
G
H
Low Output
Zero Output
High Output
Target Setpoint
I - End of
Autotune
Pk to Pk
B
Summary of Contents for XST-2-0-12-1V1-E28
Page 16: ...12 FURNACE TROUBLE SHOOTING ...
Page 27: ...ɸ ...
Page 28: ...ɸ ...
Page 29: ......
Page 30: ......
Page 31: ...3216 3208 3204 User Manual 3200 Range Process Controller HA028651 11 Aug 2012 ...
Page 170: ...User Manual 3200 Series 138 Part No HA028651 Issue 11 0 July 12 21 Certificate of Conformity ...
Page 171: ......
Page 173: ...Model 2416 Process Controller User Manual Part No HA025041_12 Date August 2014 ...
Page 174: ...This page is intentionally blank ...
Page 259: ...This page is intentionally blank ...