User Manual
3200 Series
98 Part No HA028651 Issue 11.0 July-12
Parameter
Mnemonic
Parameter Name
Modbus Address
Decimal
9 – Load Current (scaled 0 to CT Span)
uCAL
User Calibration Enable
533
A1.TYP
Alarm 1 Type
0 – Off
1 –Absolute High
2 – Absolute Low
3 – Deviation High
4 – Deviation Low
5 – Deviation Band
536
A2.TYP
Alarm 2 Type
(as Alarm 1 Type)
537
A3.TYP
Alarm 3 Type
(as Alarm 1 Type)
538
A4.TYP
Alarm 4 Type
(as Alarm 1 Type)
539
A1.LAT
Alarm 1 Latching Mode
0 – No latching
1 – Latch - Automatic Reset
2 – Latch – Manual Reset
540
A2.LAT
Alarm 2 Latching Mode
(as Alarm 1 Latching Mode)
541
A3.LAT
Alarm 3 Latching Mode
(as Alarm 1 Latching Mode)
542
A4.LAT
Alarm 4 Latching Mode
(as Alarm 1 Latching Mode)
543
A1.BLK
Alarm Blocking Mode Enable (0 = OFF, 1 = BLOCK)
544
A2.BLK
Alarm Blocking Mode Enable (0 = OFF, 1 = BLOCK)
545
A3.BLK
Alarm Blocking Mode Enable (0 = OFF, 1 = BLOCK)
546
A4.BLK
Alarm Blocking Mode Enable (0 = OFF, 1 = BLOCK)
547
Di.OP
Digital Outputs Status. This is a bitmap:
B0 – Output 1A
B1 – Output 2A
B2 – Output 3 on 32h8 and 3208 controllers
B3 – Output 4/AA
It is possible to write to this status word to use the digital outputs in a telemetry output mode. Only outputs whose
function is set to ‘none’ are affected, and the setting of any bits in the Digital Output Status word will not affect
outputs used for heat (for example) or other functions. Thus it is not necessary to mask in the settings of these bits
when writing to this variable.
551
OFS.HI Adjust
High
Offset
560
OFS.LO
Adjust Low Offset
561
PNT.HI
Adjust High Point
562
PNT.LO
Adjust Low Point
563
CT.RNG CT
Range
572
Sb.tyP
Sensor Break Type
0 – No Sensor Break
1 – Non-Latching Sensor Break
2 – Latching Sensor Break
578
Id
Customer ID – May be set to any value between 0-9999 for identification of instruments in applications. Not used by
the instrument itself.
629
PHASE
Calibration Phase
0 – None
1 – 0 mv
2 – 50 mv
3 – 150 Ohm
4 – 400 Ohm
5 – CJC
6 – CT 0 mA
7 – CT 70 mA
8 – Factory Defaults
9 – Output 1 mA low cal
10 – Output 1 mA high cal
11 – Output 2 mA low cal
768
Summary of Contents for XST-2-0-12-1V1-E28
Page 16: ...12 FURNACE TROUBLE SHOOTING ...
Page 27: ...ɸ ...
Page 28: ...ɸ ...
Page 29: ......
Page 30: ......
Page 31: ...3216 3208 3204 User Manual 3200 Range Process Controller HA028651 11 Aug 2012 ...
Page 170: ...User Manual 3200 Series 138 Part No HA028651 Issue 11 0 July 12 21 Certificate of Conformity ...
Page 171: ......
Page 173: ...Model 2416 Process Controller User Manual Part No HA025041_12 Date August 2014 ...
Page 174: ...This page is intentionally blank ...
Page 259: ...This page is intentionally blank ...