Current Transformer Input
Input current
0 to 50mA rms 48/62Hz, 10
Ω
burden resistor
fitted inside the module
Calibration
accuracy
<1% of reading (typical)
<4% of reading (worst case)
Isolation
By using external CT
Input
impedance
<20
Ω
Scale
10, 25, 50 or 100Amps
Functions
Partial load failure, SSR fault
Digital input
(DigIn A/B, B not in 3216)
Contact closure Contact open >600
Ω
Contact closed <300
Ω
Input current
<13mA
Isolation
None from PV or system
264Vac double insulated from PSU and
communications
Functions
Include alarm acknowledge, SP2 select, manual
keylock, timer functions, standby select, RSP
select
Logic I/O module
Output
Rating
On/High 12Vdc at <44mA
Off/Low <300mV at 100
μ
A
Isolation
None from PV or system
264Vac double insulated from PSU and
communications
Functions
Control, alarms or events
Logic I/O module
Digital input
Contact closure Contact open >500
Ω
Contact closed <150
Ω
Isolation
None from PV or system
264Vac double insulated from PSU and
communications
Functions
Include alarm acknowledge, SP2 select, manual
keylock, timer functions, standby select, RSP
select
Relay output channels
Type
Form A (normally open)
Rating
Min: 12V, 100mA dc Max: 2A, 264Vac resistive
Functions
Control, alarms or events
Triac output
Rating
0.75A rms 30 to 264V rms (resistive load)
Isolation
264Vac double insulated
Functions
Control, alarms or events
Analogue output
(3)
OP1, OP2 and OP3 (OP3 not available in
3216)
Rating
0-20mA into <500
Ω
Ac (<1% of r <100
μ
A) [<50
μ
A for OP3]
Resolution
13.5 bits [13.6 bits for OP3]
Isolation
264Vac double insulated from PSU and
communications.
Module code C and OP3 provides full 264V
double insulated
Functions Control,
retransmission
Note (3) Voltage output can be achieved by external adaptor
Remote SP input
Calibration Accuracy
<+ 0.25% of r 1LSD
Sample Rate
4Hz (250mS)
Isolation
264Vac double insulated from
instrument
Resolution
<0.5mV for 0-10V input, or <2
μ
A for
4-20mA
Resolution (effective
bits)
>14 bits
Drift with temperature <50ppm typical, <150ppm worst case
Common mode
rejection
48 - 62 Hz, >-120db
Series mode rejection 48 - 62 Hz, >-90db
Input Impedance
>222Kohm (Volts) 2.49R (Current)
Normal input range
0 – 10V and 4 – 20mA
Max input range
-1V to 11V and 3.36mA to 20.96mA
Software features
Control
Number of loops
1
Loop update
250mS
Control types
PID, ON/OFF, VP
Cooling types
Linear, fan, oil, water
Modes
Auto, manual, standby, forced manual
Overshoot inhibition High, low
Alarms
Number 4
Type
Absolute high and low, deviation high,
low or band, rate of change
Latching
Auto or manual latching, non-latching,
event only
Output assignment
Up to four conditions can be assigned to
one output
Setpoint programmer
Program function
1 program x 8 segments with one event
output (by using recipes five SP
programs can be stored)
Start mode
Servo from PV or SP
Power fail recovery
Continue at SP or ramp back from PV
Guaranteed soak
Inhibits dwell timing until PV within
limits
Timer
Modes
Dwell when SP reached, delayed control
action, soft start limits power below PV
threshold
Current monitor
Alarm types
Partial load failure, over current, SSR
short circuit, SSR open circuit
Indication type
Numerical or ammeter
Custom messages
Number
15 scrolling text messages
No. of characters
127 characters per message max
Languages
English, German, French, Spanish, Italian
Selection
Active on any parameter status using
conditional command
Recipes
Number
5 with 38 parameters
Selection
Key press, via communications or dig. IO
Summary of Contents for XST-2-0-12-1V1-E28
Page 16: ...12 FURNACE TROUBLE SHOOTING ...
Page 27: ...ɸ ...
Page 28: ...ɸ ...
Page 29: ......
Page 30: ......
Page 31: ...3216 3208 3204 User Manual 3200 Range Process Controller HA028651 11 Aug 2012 ...
Page 170: ...User Manual 3200 Series 138 Part No HA028651 Issue 11 0 July 12 21 Certificate of Conformity ...
Page 171: ......
Page 173: ...Model 2416 Process Controller User Manual Part No HA025041_12 Date August 2014 ...
Page 174: ...This page is intentionally blank ...
Page 259: ...This page is intentionally blank ...