3200 Series
User Manual
Part No HA028651 Issue 11.0 July-12 97
Parameter
Mnemonic
Parameter Name
Modbus Address
Decimal
End.T
Timer End Type
0 – Off
1 – Dwell at current setpoint
2- Transfer to Setpoint 2 and dwell
3 – Reset programmer when the program ends
328
SERVO
‘Servo’ Mode (programmer option only)
0 – Start first ramp from current Working Setpoint. Program must be restarted after power failure
1 - Start first ramp from current PV (temperature). Program must be restarted after power failure
2 - Start first ramp from current Working Setpoint. Program will continue to run after power failure
3 - Start first ramp from current PV (temperature). Program must be restarted after power failure
329
EVENT Event
outputs
331
P.CYCL
Number of program cycles
332
CYCLE
Currently running program cycle
333
CTRL.H
Heat/Ch1 Control Type
0 – Off
1 – On/Off Control
2 – PID Control
3 – mtr Valve Position Control
512
CTRL.C
Cool/Ch2 Control Type
0 – Off
1 – On/Off Control
2 – PID Control
513
PB.UNT Proportional
Band
Units
0 – Engineering Units
1 – Percent of Span
514
Lev2.P
Level 2 Code
515
UNITS
Display Units
0 – Degrees C
1 – Degrees F
2 – Kelvin
3 – None
4 – Percent
516
Lev3.P
Level 3 Code
517
Conf.P Config
Code
518
Cold
If set to 1 instrument will reset to factory defaults on next reset or power cycle.
519
PASS.C
Feature passcode C
520
PASS.2
Feature passcode 2
521
COOL.t
Cooling Algorithm Type:
0 – Linear
1 – Oil
2 – Water
3 – Fan
524
DEC.P
Decimal Point Position
0 – XXXX.
1 – XXX.X
2 – XX.XX
525
STBY.T Standby
Type
0 – Absolute Alarm Outputs Active – others off
1 – All outputs inactive
530
RAMP
UNITS
0 – Ramp per Minute
1 – Ramp per Hour
2 – Ramp per Second
531
Meter
(3208/3204 Only). Ammeter configuration
0 – No ammeter
1 – Heat Output (0-100%)
2 – Cool Output (0-100% cooling)
3 – Working Setpoint (scaled within SP limits)
4 – PV (scaled within range)
5 – Output Power (scaled within Op Low and OP High limits)
6 – Output centered between –100% and 100%
7 – Error (PV-SP) (scaled b/- 10 degrees)
8 – Instantaneous Amps (scaled 0 to CT Span)
532
Summary of Contents for XST-2-0-12-1V1-E28
Page 16: ...12 FURNACE TROUBLE SHOOTING ...
Page 27: ...ɸ ...
Page 28: ...ɸ ...
Page 29: ......
Page 30: ......
Page 31: ...3216 3208 3204 User Manual 3200 Range Process Controller HA028651 11 Aug 2012 ...
Page 170: ...User Manual 3200 Series 138 Part No HA028651 Issue 11 0 July 12 21 Certificate of Conformity ...
Page 171: ......
Page 173: ...Model 2416 Process Controller User Manual Part No HA025041_12 Date August 2014 ...
Page 174: ...This page is intentionally blank ...
Page 259: ...This page is intentionally blank ...