6
Commissioning
30
The gateway will now restart and the status LED will flash blue during
the start-up process. As soon as the gateway is ready for operation,
the status LED lights up solid green.
6.6.4
Carrying out firmware updates
1
Disconnect the BT Gateway for testo 182 from the power supply.
2
Remove USB wireless stick.
3
Insert USB flash drive with the firmware update package (at highest
folder level) into USB 2.
4
Connect BT Gateway for testo 182 to the power supply.
Update is carried out automatically.
•
Update successful: LED flashes green 10 times and gateway shuts
down
•
Update failed: LED flashes red 5 times
•
Error with update: repeat steps 1 to 4. Make sure that the firmware
update package was correctly saved on the USB flash drive.
5
Remove USB flash drive with the firmware update package from the
USB port.
5
Reinsert USB wireless stick into USB 2.
6
Restart BT Gateway for testo 182 with the new firmware: unplug and
plug in the power supply.
The Gateway is now ready for operation.
6.7
Commissioning testo Saveris software
6.7.1
Installing testo Saveris software
Before the installation: End all running programs.
Administrator rights are required for installation.
Log in directly as the administrator, not via
Execute as…
.
If you are installing multiple clients in a network, make sure that no
simultaneous changes are made to the system configuration by the
clients during simultaneous operation of them.