NO/NC SELECTED
This parameter defines whether the switching output is in a normally open (NO) or
normally closed (NC) configuration. A value of 0 sets it to NO, while a value of 1 sets it to
NC. The default setting value is 0 (NO).
Slave ID
: 1 to 247
Address location
: 26
Value
: 0 or 1 (value 0 for NO and 1 for NC select, default 0)
BACKGROUND DISTANCE
This parameter holds the background distance. The following cases apply: (1) the
parameter can be read back after using the teach-in buttons to program the device; (2) it
can be programmed using Modbus function 06 Write single register.
Slave ID
: 1 to 247
Address location
: 28
Value
: 500 to 12 500 (in millimeters, default 0)
THRESHOLD 1 DISTANCE
This parameter holds the threshold 1 distance. The following cases apply: (1) the
parameter can be read back after using the teach-in buttons to program the device; (2) it
can be programmed using Modbus function 06 Write single register.
Slave ID
: 1 to 247
Address location
: 30
Value
: 500 to 12 500 (in millimeters, default 0)
THRESHOLD 2 DISTANCE
This parameter holds the threshold 2 distance. The following cases apply: (1) the
parameter can be read back after using the teach-in buttons to program the device; (2) it
can be programmed using Modbus function 06 Write single register.
Slave ID
: 1 to 247
Address location
: 32
Value
: 500 to 12 500 (in millimeters, default 0)