In this page current harmonic control mode can be made
active or passive, harmonic of current and delay can be set.
When the setting is active color of the button's writing
becomes green, when it is passive it becomes red. When the
control mode is active and the total voltage harmonics
get higher than the setted harmonic values, the device waits
as much as delay; after the time of the delay comes to an end
it makes the compensation stop and ''High Harmonic Current'' warning comes to the
screen. Also ''ALR1''
is on. When the control mode is passive, the device doesn't make
voltage harmonic control.
OK
THDI Protection Settings
Delay (sn.)
THDI Set (%)
20
40
TURN BACK
THDI Control Mode Active
3.3
Current Harmonic Protection
3.4
Generator Compensation Setting
In this page generator control mode can be made passive
or active and inductive/active can be set. When the setting is
active color of the button's writing becomes green, when it is
passive it becomes red. When the generator mode is
activated, the device compensates according to the set
“inductive set value” while the generator is on.
W
hen the
generator mode is passive, compensation is stopped while
the generator is on.
OK
Generator Settings
Inductive Set (PF)
10
Generator Control Mode Active
TURN BACK
In this page Voltage control mode can be made passive or
active, High voltage and low voltage values can be set. When
the setting is active color of the button's writing becomes
green, when it is passive it becomes red. When the voltage
control mode is active, it stops the compensation if Set
voltage get out of upper and lower limits. Then the display
will show "High Voltage" or "Low Voltage" warning.
OK
Voltage Protection Settings
Low Voltage (V)
High Voltage (V)
120
240
TURN BACK
Voltage Control Mode Passive
3.5
Voltage Protection
Pressing the ''Confirm'' button, the saved data is recorded and returns to ''Settings'' page.
When the ''Return'' button is pressed, without recording any value,
turns to ''Settings'' page.
11
Pressing the ''Confirm'' button, the saved data is recorded and returns to ''Settings'' page.
When the ''Return'' button is pressed, without recording any value,
turns to ''Settings'' page.
Pressing the ''Confirm'' button, the saved data is recorded and returns to ''Settings''
page. When the ''Return'' button is pressed, without recording any value,
turns to
''Settings'' page.
Settings
E
Settings
E
Settings
E
Also ''ALR1''is on. When the Voltage Protection mode is passive, the device doesn't make
voltage control.