Motivity v1.3
Technical Documentation
The objects of the second Output Object start at 11. There is a spacing of 4 objects between
each Output Action.
©
Tense BVBA
15/03/17
9
Name
1 second, 1 minute, 1 Hour
Yes/No
0-750
Yes/No
Yes/No
Yes/No
Value Range
Comment
Value Type
1bit, 1 Byte Scaling[0-100%], 1
Byte unsigned [0-255], Scene
[1-64], 2 Byte unsigned [0-
65535]
type of value to send with this output action
ON Value to send on Start
depending on value type
value to send when motion is detected
OFF Value to send at End of
Switch Off Delay
depending on value type
value to send when switch off delay has
elapsed
Base Switch Off Delay
Time Base for Switch Off Delay Time
Time Factor Switch Off Delay
1 to 240
factor to multiply Time Base Switch Off
Delay Time
Depending on Brightness Value
the action is depending on the (internal or
external)lux value
Lux Threshold
threshold value under which the light is
switched on
Use internal sensor
Use internal brightness sensor, or a value
from an external sensor, received over the
bus
Use Safety Pause
ignore motion detector input for 2 seconds
after a '1' telegram was received on the
“Safety Pause Input” object
Activation
Always Active, Active on 1,
Active on 0
(de)activate this Output Action
Send OFF Value upon deactivation
Send OFF value when Output Action is
active and deselected