Brightness Sensor
To get information about the measured light intensity, you can query the brightness sensor.
Due to tolerances in the brightness sensor electronics, it might be necessary to correct the
measured value.
If you want to switch on a certain brightness level (e.g for determing the difference between
day/night), you can use the Threshold value switch communication object. A
If the Lux Hysteresis is different from 0, then the switch object will be set to 0 only when the
measured light level is below the threshold minus hysteresis value.
©
Tense BVBA
15/03/17
12
Name
Value Range
Comment
Correction for Lux Value
-127,128
correct on the measured brightness value
0-60
send the lux value cyclically
0-750
threshold level
Hysteresis
0-255
hysteresys value
Send at least every …
minute(s)
Threshold value for switch
object
No Name
I/O DPT
Flags
Use
3
Lux Value
O DPT9.4
CRT
measured brightness value
4
Lux Threshold Switch
O DPT1.1
CT
threshold value has been surpassed