Output
With each Output Action you can specify which action to perform when motion is detected,
allowing you to e.g.
–
switch on/off a 1-Bit actuator
–
adjust the dimming to a fixed absolute value
–
recall a scene
–
send an (unsigned) 1 or 2 Byte value
–
etc...
You can also specify a switch-off delay. This is the time after the last detection that the Motivity
will wait to perform the turn off action.
It's also possible to make the action depending on a maximum brightness value. When the
light level, from the internal or external sensor, is above this threshold, then the motivity will
ignore the motion event.
Output Actions can be selected at runtime. This allows you to specify a different behaviour at a
different time or in different conditions. When an Output Action is deactivated, it might be
useful to turn off the light sources it controls. If this is necessary, set “Send OFF on
deactivation” to “Yes”.
The safety pause parameter will disable the motion detection for 2 seconds. This might be
useful if a different light source is in the field of the detector, and switching on of this light
sources causes the detector to trigger on it.
List of parameters and communication objects:
©
Tense BVBA
15/03/17
8
No Name
I/O DPT
Flags
Use
7
Switch Value 1bit
O DPT1.1 CT
1 bit Output from Output Object1
7
Value 1 Byte Scaling
O DPT5.1 CT
7
Value 1 Byte
O DPT5.10 CT
Unsigned 1 Byte Output from Output Object1
7
Scene
O DPT17.1 CT
Scene value from Output Object1
7
Value 2 Byte
O DPT7.1 CT
Unsigned 2 Byte Output from Output Object1
8
External Lux Value
I DPT9.4 CW
Value if external light sensor is used
9
Safety Pause Input
I DPT1.1 CW
Input for ignoring briefly motion detector
10
Object Selection
I DPT1.1 CW
Input for (de)activating the Output Object
1 Byte Scaling Output from Output Object1,
typically used for dimming