iRIS8 - Addressable Fire Alarm Panel
– Installer Programming
47
3.3.9. Network Type Input
Select this type, when the input will be activated from a network device (panel/repeater number).
Press MORE button to access the additional settings for
the network type input. Note that all introduced changes
must be confirmed with APPLY button in this main screen.
Set the GROUP Number from 1-250, according the
system configuration.
Other important settings for network type are:
-
OUTPUT NUMBER
. Enter a number of an output from 1
to 250.
-
PANEL/REPEATER NUMBER
. Enter a number of
panel or repeater from 1 to 64.
3.3.10. Zone Group Type Input
Select this type, when the input will be activated from a zone in fire alarm or fault, included in a group.
Press MORE button to access the additional settings for
the zone group type input. Note that all introduced
changes must be confirmed with APPLY button in this
main screen.
Set the GROUP Number from 1-250, according the
system configuration.
Next, set ZONE GROUP NUMBER from 1 to 200.
In ALARMS COUNTER field enter a number (1-9) of
registered fire alarms, when after reaching their count, the
input will be activated.
Note: The ALARMS COUNTER
field is set only for ZONE FIRE event type.
In FUNCTION field set the logic for operation OR/AND.
The possible zone group events for activation of the input
are listed after pressing the active button for FUNCTION
selection:
-
ZONE FIRE
- Activation from a zone in fire alarm
included in a group.
-
ZONE FAULT
- Activation from a zone in fault included
in a group.