iRIS8 - Addressable Fire Alarm Panel
– Installer Programming
45
3.3.7. Action Type Input
Select this type, when the input will be activated from an action event. Press MORE button to access the additional
settings for the action type input. Note that all introduced changes must be confirmed with APPLY button in this main
screen.
Set the GROUP Number from 1-250, according the
system configuration. Press EXIT to return back.
Press the active button for the respective action event.
The selected action event is automatically set into the
FUNCTION section at the main screen.
The possible action events for activation of the input are
listed after pressing the active button for FUNCTION
selection:
-
SILENCE BUZZER
- Activation in case of silencing the
buzzer in the system.
-
SILENCE SOUNDER
- Activation in case of silencing
the sounders in the system.
-
RESET
- Activation in case of reset in the system.
-
SOUNDER ON
- Activation in case of sounders
activation in the system.
-
FIRE BRIGADE ON
- Activation in case of Fire Brigade
monitored output activation.
-
FAULT OUTPUT ON
- Activation in case of Fault
monitored output activation.
-
FIRE PROTECTION ON
- Activation in case of Fire
Protection monitored output activation.
-
SOUNDER ON (ZONAL)
- Activation in case of sounder
activation in a zone.
-
DAY MODE
- Activation in case of switching to DAY
Operation mode.
-
NIGHT MODE
- Activation in case of switching to
NIGHT Operation mode.
In case for the action event type is set function SOUNDER ON (ZONAL), the installer must set also and zone number in
the additional settings screen.