iRIS8 - Addressable Fire Alarm Panel
– Installer Programming
16
It is recommended to arrange the Sounder Groups
and to associate the sounders to the respective
zone numbers in advance.
Zone
No
Sounder
Group
Sounder
No
Panel Settings
(Sounder GROUP
menu)
1
1
SND 1
GROUP A: 2
GROUP B: 3
GROUP C: 0
2
2
SND 2
SND 3
SND 4
GROUP A: 1
GROUP B: 3
GROUP C: 0
3
3
SND 5
SND 6
SND 7
GROUP A: 1
GROUP B: 2
GROUP C: 0
The used numbers for Sounder Groups and Zones
in the example are illustrative. It is not required the
numbers for Sounder Groups and Zones to match.
This approach is used to make the presented
example clearer.
To exit from the ZONES submenu press EXIT button.
3.1.5. Zones
– Quick Review
Next to ZONES menu is situated button << GRID VIEW for quick reviewing the operation status of all zones. The zones
are reviewed at several screens, as 60 numbers are displayed at the same time.
First are displayed the zone numbers from 1 to 60.
The Enabled zone numbers are presented with active
button in blue. The Disabled zone numbers are presented
with active button in white.
For quick access to a zone setting menu, press its
number. To go back from zone menu to grid view menu,
press EXIT button.
To review the zone numbers from 61 to 120, press down
arrow button. Press button again to review zones from
121 to 180, etc. Press the up arrow button to move back.
Every change of the operation status of the zones is
updated immediately in the Grid View menu.
To exit from the << GRID VIEW menu press EXIT button.
3.2. Devices
Enter DEVICES menu. The menu includes submenus for settings and programming of periphery and loop devices, as
the ways for addressing of loop devices.
Quick summery for the submenus:
- Settings for Loop Devices (item
-
Quick review of the loop devices’ status by
address number (item
- Addressing of loop devices (item
- Settings for Periphery Devices (item