2105 Interface Module
Section 3 Modbus Protocol and 2100 Output
3-10
1618
Rainfall Intensity status code
16-bit integer
Read
1619-1622
Rainfall Intensity time record
Time
Read
a.
A write to the Identify module register will cause the module to perform the identify operation which may be a steady
LED for a few seconds or a beep in the Field Wizard.
b.
Setting the Take Reading flag to 1 will cause the module to update the registers with current data readings. It will
be set to zero when the readings have all been updated. This may be used to initiate readings and poll for when
they are ready to be read. It may take up to 50 seconds to update all the readings, depending upon the flow condi-
tions. Setting the Take Reading flag to 2 causes an automatic, 15 second update of readings when a Modbus mas-
ter is polling the 2100.
c.
The Update Interval specifies an interval in seconds that the registers are automatically updated. It defaults to zero,
which indicates that no automatic updating will occur.
d.
The Active Flag (1-4) bit fields specify what fields/registers are active in the list. This provides support for a maxi-
mum of 64 fields. For example, if bit 0 of register 27 is set, the Level (registers 40,41) is active. If bit 1 of register
27 is set, then the Velocity (registers 55,56) is active. If bit 0 of register 28 is set, the Analog channel 7 (registers
265,266) is active.
e.
A non-zero status code indicates a measurement problem.
f.
Time is represented in a series of registers: Order is from lowest address to highest - Seconds (0-59), Minutes
(0-59), Hours (0-23), Days (1-31), Month (1-12) and Year (1977-2099).
Table 3-2 Modbus ASCII Address 2 +(N - 1) Register Definitions (Continued)
Register Number(s)
Name
Data Type
Units
Read/Write
Summary of Contents for 2105
Page 2: ......
Page 4: ......
Page 10: ...2105 Interface Module Table of Contents viii ...
Page 58: ...2105 Interface Module Section 2 Installation and Operation 2 40 ...
Page 70: ...2105 Interface Module Section 3 Modbus Protocol and 2100 Output 3 12 ...
Page 74: ...2105 Interface Module Section 4 Maintenance 4 4 ...
Page 77: ...2105 Interface Module Appendix A Replacement Parts List A 3 Drawing 602002586 ...
Page 78: ...2105 Interface Module Appendix A Replacement Parts List A 4 Drawing 602002586 ...
Page 79: ...2105 Interface Module Appendix A Replacement Parts List A 5 ...
Page 80: ...2105 Interface Module Appendix A Replacement Parts List A 6 ...
Page 82: ...2105 Interface Module Appendix A Replacement Parts List A 8 ...
Page 84: ...2105 Interface Module Appendix A Replacement Parts List A 10 ...
Page 94: ...2105 Interface Module Appendix C Material Safety Data Sheets C 8 ...
Page 98: ......